MAXScanner calculator widget
Generator Sizing Calculator — kW, kVA & Motor Starting Load
Editable live calculator
Change any input — the result updates immediately
No hidden assumptions. Inputs, units and the working stay visible so you can check the calculation.
Calculated result
151.32 kVA minimum planning size
Running load: 50 kVA (40 kW at PF 0.8)
Motor-start scenario: 125 kVA
Governing case: Motor-start scenario
Equivalent real power at entered PF: 121.05 kW
Approximate rated current at 415 V 3φ: 210.51 A
Show the working
- 1. Running kVA = 40 kW ÷ 0.8 = 50 kVA.
- 2. Other running load = 50 − 15 = 35 kVA.
- 3. Motor starting demand = 15 × 6 = 90 kVA.
- 4. Starting scenario = 35 + 90 = 125 kVA.
- 5. Governing demand = max(50, 125) = 125 kVA.
- 6. Required size = 125 × 1.15 ÷ 0.95 = 151.32 kVA.
More actions
Shared links reopen these inputs. Recent and saved calculations stay in this browser unless you clear site data.