Generator Sizing Calculator — kW, kVA & Motor Starting Load

Open full guide ↗

Editable live calculator

Change any input — the result updates immediately

No hidden assumptions. Inputs, units and the working stay visible so you can check the calculation.

Calculated result

151.32 kVA minimum planning size

Running load: 50 kVA (40 kW at PF 0.8)

Motor-start scenario: 125 kVA

Governing case: Motor-start scenario

Equivalent real power at entered PF: 121.05 kW

Approximate rated current at 415 V 3φ: 210.51 A

Show the working
  1. 1. Running kVA = 40 kW ÷ 0.8 = 50 kVA.
  2. 2. Other running load = 50 − 15 = 35 kVA.
  3. 3. Motor starting demand = 15 × 6 = 90 kVA.
  4. 4. Starting scenario = 35 + 90 = 125 kVA.
  5. 5. Governing demand = max(50, 125) = 125 kVA.
  6. 6. Required size = 125 × 1.15 ÷ 0.95 = 151.32 kVA.