MAXScanner calculator widget
Transformer All-Day Efficiency Calculator — 24-Hour Load Profile
Editable live calculator
Change any input — the result updates immediately
No hidden assumptions. Inputs, units and the working stay visible so you can check the calculation.
Calculated result
95.053% all-day efficiency
Output energy: 880 kWh
Core-loss energy: 28.8 kWh
Copper/load-loss energy: 17 kWh
Total loss energy: 45.8 kWh
Input energy: 925.8 kWh
Time-weighted average loading: 45.83%
Entered energized profile: 24 h
Period 1: 6 h × 100% × PF 0.8 → 480 kWh output, 12 kWh copper loss
Period 2: 10 h × 50% × PF 0.8 → 400 kWh output, 5 kWh copper loss
Period 3: 8 h × 0% × PF 0 → 0 kWh output, 0 kWh copper loss
Model boundary: core loss accrues only for entered energized hours. Add a 0% load period for energized no-load time; omit hours only when the transformer is de-energized.
Show the working
- 1. Output energy = Σ(kVA × load fraction × PF × hours) = 880 kWh.
- 2. Core-loss energy = 1.2 kW × 24 h = 28.8 kWh.
- 3. Copper-loss energy = Σ(2 kW × load fraction² × hours) = 17 kWh.
- 4. Input energy = 880 + 45.8 = 925.8 kWh.
- 5. ηall-day = 880 ÷ 925.8 × 100 = 95.0529%.
More actions
Shared links reopen these inputs. Recent and saved calculations stay in this browser unless you clear site data.