Skip to main content

MAXScanner calculator widget

Transformer All-Day Efficiency Calculator — 24-Hour Load Profile

Open full guide ↗

Editable live calculator

Change any input — the result updates immediately

No hidden assumptions. Inputs, units and the working stay visible so you can check the calculation.

Calculated result

95.053% all-day efficiency

Output energy: 880 kWh

Core-loss energy: 28.8 kWh

Copper/load-loss energy: 17 kWh

Total loss energy: 45.8 kWh

Input energy: 925.8 kWh

Time-weighted average loading: 45.83%

Entered energized profile: 24 h

Period 1: 6 h × 100% × PF 0.8 → 480 kWh output, 12 kWh copper loss

Period 2: 10 h × 50% × PF 0.8 → 400 kWh output, 5 kWh copper loss

Period 3: 8 h × 0% × PF 0 → 0 kWh output, 0 kWh copper loss

Model boundary: core loss accrues only for entered energized hours. Add a 0% load period for energized no-load time; omit hours only when the transformer is de-energized.

Show the working
  1. 1. Output energy = Σ(kVA × load fraction × PF × hours) = 880 kWh.
  2. 2. Core-loss energy = 1.2 kW × 24 h = 28.8 kWh.
  3. 3. Copper-loss energy = Σ(2 kW × load fraction² × hours) = 17 kWh.
  4. 4. Input energy = 880 + 45.8 = 925.8 kWh.
  5. 5. ηall-day = 880 ÷ 925.8 × 100 = 95.0529%.
More actions

Shared links reopen these inputs. Recent and saved calculations stay in this browser unless you clear site data.