MAXScanner calculator widget
Transformer Fault Current Calculator — kA from kVA & %Z
Editable live calculator
Change any input — the result updates immediately
No hidden assumptions. Inputs, units and the working stay visible so you can check the calculation.
Calculated result
27.824 kA
Rated current: 1,391.21 A
Fault-current multiplier: 20×
Transformer-limited fault level: 20 MVA
Equivalent transformer impedance: 8.611 mΩ
Show the working
- 1. Rated current = 1,000×1000 ÷ (√3×415) = 1,391.205 A.
- 2. Per-unit impedance = 5 ÷ 100 = 0.05.
- 3. Terminal fault current = 1,391.205 ÷ 0.05 = 27,824.11 A = 27.824 kA.
- 4. Fault level = 1,000 kVA × 100 ÷ 5 = 20 MVA.
Transformer-terminal infinite-bus estimate only. It excludes utility/source impedance, conductor and bus impedance, motor contribution, grounding/zero-sequence networks, X/R asymmetry and arc-flash energy. Use the actual nameplate %Z and a proper short-circuit study for equipment ratings.
More actions
Shared links reopen these inputs. Recent and saved calculations stay in this browser unless you clear site data.