Transformer Parallel Load Sharing Calculator — kVA & Impedance

Open full guide ↗

Editable live calculator

Change any input — the result updates immediately

No hidden assumptions. Inputs, units and the working stay visible so you can check the calculation.

Calculated result

A 797.55 kVA · B 502.45 kVA

Transformer A loading: 79.75%

Transformer B loading: 79.75%

Combined nameplate capacity: 1,630 kVA

Bank loading by nameplate sum: 79.75%

Maximum total load before Transformer A reaches 100%: 1,630 kVA

Show the working
  1. 1. Admittance weight A = kVA/Z% = 1,000 ÷ 6 = 166.667.
  2. 2. Admittance weight B = kVA/Z% = 630 ÷ 6 = 105.
  3. 3. A share = 1,300 × 166.667 ÷ (166.667 + 105) = 797.55 kVA.
  4. 4. B share = 1,300 − 797.55 = 502.45 kVA.
  5. 5. Loading = assigned kVA ÷ nameplate kVA × 100 → A 79.75%, B 79.75%.