Transformer Parallel Load Sharing Calculator — kVA & Impedance
Editable live calculator
Change any input — the result updates immediately
No hidden assumptions. Inputs, units and the working stay visible so you can check the calculation.
Calculated result
A 797.55 kVA · B 502.45 kVA
Transformer A loading: 79.75%
Transformer B loading: 79.75%
Combined nameplate capacity: 1,630 kVA
Bank loading by nameplate sum: 79.75%
Maximum total load before Transformer A reaches 100%: 1,630 kVA
Show the working
- 1. Admittance weight A = kVA/Z% = 1,000 ÷ 6 = 166.667.
- 2. Admittance weight B = kVA/Z% = 630 ÷ 6 = 105.
- 3. A share = 1,300 × 166.667 ÷ (166.667 + 105) = 797.55 kVA.
- 4. B share = 1,300 − 797.55 = 502.45 kVA.
- 5. Loading = assigned kVA ÷ nameplate kVA × 100 → A 79.75%, B 79.75%.