How to use this calculator
- Enter measured or design values using the units shown beside each field.
- Review the live results and the substituted calculation steps before using the estimate.
- Check the assumptions below, then continue to a related calculator when the next engineering decision needs another model.
Worked example
A chiller delivering 1,000 kW cooling at 200 kW input rejects about 1,200 kW at the condenser before any separately entered auxiliary heat.
Assumptions and limits
- Steady-state energy balance excludes auxiliary heat unless explicitly added.
- Use measured simultaneous load and power for operating diagnostics.