How to use this calculator
- Enter measured or design values using the units shown beside each field.
- Review the live results and the substituted calculation steps before using the estimate.
- Check the assumptions below, then continue to a related calculator when the next engineering decision needs another model.
Worked example
Cooling 2,000 kg/h condensate from 90°C to 50°C releases about 93 kW of sensible heat using Cp=4.186 kJ/kg-K.
Assumptions and limits
- Sensible liquid cooling only; flash steam and phase change require a steam-property calculation.
- Use an appropriate liquid heat capacity when chemistry or temperature makes the water approximation unsuitable.