Formula & worked example
εs=(Ts−To)/(Ti−To); Qs=ṁcpεs(Ti−To); Ql=ṁhfgεl(Wi−Wo).
At 1 kg/s, 70% sensible effectiveness and a 20 K indoor-outdoor difference recovers about 14.1 kW sensible heat.
Help improve MAXScanner?
Optional usage analytics can tell us which tools and workflows are useful. File names, document contents, typed values, search queries and workflow tokens are not sent.
HVAC engineering calculator · Updated Sep 17, 2026
Estimate sensible and latent energy-recovery effectiveness, supply leaving conditions and recovered sensible/latent load from airflow and indoor/outdoor states.
εs=(Ts−To)/(Ti−To); Qs=ṁcpεs(Ti−To); Ql=ṁhfgεl(Wi−Wo).
At 1 kg/s, 70% sensible effectiveness and a 20 K indoor-outdoor difference recovers about 14.1 kW sensible heat.
Estimate sensible and latent energy-recovery effectiveness, supply leaving conditions and recovered sensible/latent load from airflow and indoor/outdoor states.
Use it as an auditable engineering cross-check. Final selections should use measured design conditions, manufacturer data, applicable standards and local code.
HVAC shortcuts can hide density, pressure, concentration and effectiveness assumptions. Exposing them makes the result easier to verify and revise.