Formula & example
Qs≈1.08·CFM·ΔT°F BTU/h for standard air.
1,000 CFM with a 20°F temperature change transfers about 21,600 BTU/h or 1.8 refrigeration tons sensibly.
HVAC engineering calculator · Updated Sep 17, 2026
Calculate sensible air-side heat transfer from airflow and temperature difference, with BTU/h, kW and tons outputs.
Qs≈1.08·CFM·ΔT°F BTU/h for standard air.
1,000 CFM with a 20°F temperature change transfers about 21,600 BTU/h or 1.8 refrigeration tons sensibly.
Calculate sensible air-side heat transfer from airflow and temperature difference, with BTU/h, kW and tons outputs.
Yes. The calculator exposes the unit basis in the inputs and reports useful cross-unit outputs where the engineering workflow benefits from them.
No. It is a transparent deterministic engineering calculator for sizing, diagnostics and cross-checks. Final equipment, duct and refrigeration decisions should use measured conditions, manufacturer data and applicable codes or standards.