LMTD Calculator — Counterflow & Parallel Heat Exchanger

Calculate terminal temperature differences and log mean temperature difference for counterflow or parallel-flow heat exchangers.

Last updated: September 17, 2026

Results

Temperature differences must stay positive; check for temperature cross

Formula, example and assumptions

LMTD=(ΔT1−ΔT2)/ln(ΔT1/ΔT2).

Counterflow 150→80 °C hot and 30→90 °C cold gives ΔT1=60 K, ΔT2=50 K and LMTD≈54.85 K.

  • No temperature cross is permitted in this simple sensible-heat model.
  • For multipass or crossflow equipment apply an appropriate correction factor F.