How to use this calculator
- Enter measured or design values using the units shown beside each field.
- Review the live results and the substituted calculation steps before using the estimate.
- Check the assumptions below, then continue to a related calculator when the next engineering decision needs another model.
Worked example
At 50 L/s and 20 m excess valve head, water loses about 9.8 kW hydraulically before pump and motor efficiency are considered.
Assumptions and limits
- This isolates excess throttling head; a VFD retrofit must be checked against the full system and pump curves.
- Minimum speed, static head, control authority, motor cooling and process constraints can limit savings.
- Do not substitute a simple cube-of-flow estimate for a real system-curve/load-profile comparison where static head is material.