Formula & example
QBTU/h≈500·GPM·ΔT°F; tons=Q/12000.
At 10°F ΔT, 24 tons needs about 57.6 GPM of water.
HVAC engineering calculator · Updated Sep 17, 2026
Calculate chilled-water flow from cooling load and temperature difference, or show the carried load for an entered GPM.
QBTU/h≈500·GPM·ΔT°F; tons=Q/12000.
At 10°F ΔT, 24 tons needs about 57.6 GPM of water.
Calculate chilled-water flow from cooling load and temperature difference, or show the carried load for an entered GPM.