Formula & example
QBTU/h≈500·GPM·ΔT°F; tons=Q/12000.
At 10°F ΔT, 24 tons needs about 57.6 GPM of water.
Help improve MAXScanner?
Optional usage analytics can tell us which tools and workflows are useful. File names, document contents, typed values, search queries and workflow tokens are not sent.
HVAC engineering calculator · Updated Sep 17, 2026
Calculate chilled-water flow from cooling load and temperature difference, or show the carried load for an entered GPM.
QBTU/h≈500·GPM·ΔT°F; tons=Q/12000.
At 10°F ΔT, 24 tons needs about 57.6 GPM of water.
Calculate chilled-water flow from cooling load and temperature difference, or show the carried load for an entered GPM.
Yes. The calculator exposes the unit basis in the inputs and reports useful cross-unit outputs where the engineering workflow benefits from them.
No. It is a transparent deterministic engineering calculator for sizing, diagnostics and cross-checks. Final equipment, duct and refrigeration decisions should use measured conditions, manufacturer data and applicable codes or standards.