Condenser Water Flow Calculator — Heat Rejection, Range & GPM

Calculate condenser-water flow from heat rejection and water temperature range, with SI and US flow outputs.

Inputs

Live engineering result

Mass flow 43.434826 kg/s
Water flow 43.565523 L/s
Water flow 156.83588 m³/h
Water flow 690.52761 US gpm

Formula & worked example

m=Q/(Cp·ΔT); volumetric flow=m/ρ.

1,000 kW rejected across a 5.5°C water range requires about 43.5 L/s for water.

Assumptions & limits

  • Uses entered water density and specific heat.
  • Condenser heat rejection is cooling load plus compressor/equipment heat, not cooling load alone.

Frequently asked questions

What does this Condenser Water Flow Calculator calculate?

Calculate condenser-water flow from heat rejection and water temperature range, with SI and US flow outputs.

Can I use the result for equipment selection?

Use the result as an engineering screening and cross-check. Confirm final selections against manufacturer performance data, design conditions, applicable standards and local code.