Formula & worked example
ṁwater=ṁdry-air·(Win−Wout); Qlatent=ṁwater·hfg.
5,000 CFM at 1.2 kg/m³ with humidity ratio falling from 0.012 to 0.008 removes about 40.8 kg/h of water.
Help improve MAXScanner?
Optional usage analytics can tell us which tools and workflows are useful. File names, document contents, typed values, search queries and workflow tokens are not sent.
HVAC design calculator · Updated Sep 17, 2026
Estimate cooling-coil condensate from dry-air flow and entering/leaving humidity ratio, with kg/h, L/h, US gal/h and equivalent latent cooling load.
ṁwater=ṁdry-air·(Win−Wout); Qlatent=ṁwater·hfg.
5,000 CFM at 1.2 kg/m³ with humidity ratio falling from 0.012 to 0.008 removes about 40.8 kg/h of water.
Estimate cooling-coil condensate from dry-air flow and entering/leaving humidity ratio, with kg/h, L/h, US gal/h and equivalent latent cooling load.
Use the result as a transparent engineering cross-check. Confirm final selections against measured design conditions, manufacturer data, applicable standards and local code.
HVAC shortcuts can look precise while hiding density, efficiency, free-area or pressure assumptions. MAXScanner keeps the governing inputs visible so the result can be audited.