Formula & worked example
ṁwater=ṁdry-air·(Win−Wout); Qlatent=ṁwater·hfg.
5,000 CFM at 1.2 kg/m³ with humidity ratio falling from 0.012 to 0.008 removes about 40.8 kg/h of water.
HVAC design calculator · Updated Sep 17, 2026
Estimate cooling-coil condensate from dry-air flow and entering/leaving humidity ratio, with kg/h, L/h, US gal/h and equivalent latent cooling load.
ṁwater=ṁdry-air·(Win−Wout); Qlatent=ṁwater·hfg.
5,000 CFM at 1.2 kg/m³ with humidity ratio falling from 0.012 to 0.008 removes about 40.8 kg/h of water.
Estimate cooling-coil condensate from dry-air flow and entering/leaving humidity ratio, with kg/h, L/h, US gal/h and equivalent latent cooling load.
Use the result as a transparent engineering cross-check. Confirm final selections against measured design conditions, manufacturer data, applicable standards and local code.
HVAC shortcuts can look precise while hiding density, efficiency, free-area or pressure assumptions. MAXScanner keeps the governing inputs visible so the result can be audited.