Formula & worked example
ṁwater=ṁdry-air·(Wtarget−Win); ṁair≈ρ·Q.
5,000 CFM at 1.20 kg/m³ with humidity ratio rising from 0.004 to 0.008 kg/kg requires about 40.8 kg/h of added moisture.
Help improve MAXScanner?
Optional usage analytics can tell us which tools and workflows are useful. File names, document contents, typed values, search queries and workflow tokens are not sent.
HVAC engineering calculator · Updated Sep 17, 2026
Size first-pass humidification moisture capacity from airflow and entering/target humidity ratio, with kg/h, lb/h and water L/h outputs.
ṁwater=ṁdry-air·(Wtarget−Win); ṁair≈ρ·Q.
5,000 CFM at 1.20 kg/m³ with humidity ratio rising from 0.004 to 0.008 kg/kg requires about 40.8 kg/h of added moisture.
Size first-pass humidification moisture capacity from airflow and entering/target humidity ratio, with kg/h, lb/h and water L/h outputs.
HVAC results depend on air properties, measured conditions and design conventions. MAXScanner exposes the governing assumptions so the result can be checked instead of hiding them behind a single number.
No. Use it for transparent sizing and cross-checking, then verify final selections against measured conditions, equipment data and applicable design standards.