Formula & worked example
ṁwater=ṁdry-air·(Wtarget−Win); ṁair≈ρ·Q.
5,000 CFM at 1.20 kg/m³ with humidity ratio rising from 0.004 to 0.008 kg/kg requires about 40.8 kg/h of added moisture.
HVAC engineering calculator · Updated Sep 17, 2026
Size first-pass humidification moisture capacity from airflow and entering/target humidity ratio, with kg/h, lb/h and water L/h outputs.
ṁwater=ṁdry-air·(Wtarget−Win); ṁair≈ρ·Q.
5,000 CFM at 1.20 kg/m³ with humidity ratio rising from 0.004 to 0.008 kg/kg requires about 40.8 kg/h of added moisture.
Size first-pass humidification moisture capacity from airflow and entering/target humidity ratio, with kg/h, lb/h and water L/h outputs.
HVAC results depend on air properties, measured conditions and design conventions. MAXScanner exposes the governing assumptions so the result can be checked instead of hiding them behind a single number.
No. Use it for transparent sizing and cross-checking, then verify final selections against measured conditions, equipment data and applicable design standards.