Estimate evaporation from circulation/range or measured heat rejection, and show annual water loss with an explicit latent-heat assumption.

Inputs

Live results

  • Heat rejection 5,802.2611 kW
  • Evaporation 8.5428571 m³/h
  • Evaporation fraction 0.85428571%
  • Annual evaporation 51,257.143 m³

Formula

E≈Qreject/hfg; Q≈ṁwater·Cp·range.

Worked example

1,000 m³/h water cooled by 5 K rejects about 5.8 MW and evaporates roughly 9.4 m³/h at hfg=2,450 kJ/kg.

Assumptions and limits

  • Neglects sensible heat transfer to air in the simple heat-balance estimate.
  • Use site water temperature for density and latent heat when precision matters.

FAQs

What does this Cooling Tower Evaporation Loss Calculator calculate?

Estimate evaporation from circulation/range or measured heat rejection, and show annual water loss with an explicit latent-heat assumption.

What should I verify before final design?

Verify measured operating data, fluid properties, equipment curves, safety margins and the applicable OEM or engineering standard.

Why are intermediate results shown?