Cooling Tower Fan Affinity Calculator — VFD Speed, Airflow, Pressure & Power
Estimate cooling-tower fan airflow, pressure and power at a new speed using affinity laws, with annual energy difference for VFD screening.
Inputs
Live results
- Speed ratio 0.8
- New airflow 80,000
- New pressure 160
- New ideal power 15.36 kW
- Annual energy difference 73.2 MWh
Formula
Q₂/Q₁=N₂/N₁; ΔP₂/ΔP₁=r²; P₂/P₁=r³.
Worked example
Reducing a 30 kW fan from 100% to 80% speed gives about 15.36 kW ideal affinity power.
Assumptions and limits
- Affinity laws assume similar system/fan behavior and unchanged geometry.
- Minimum tower airflow and thermal performance must be checked separately.
FAQs
What does this Cooling Tower Fan Affinity Calculator calculate?
Estimate cooling-tower fan airflow, pressure and power at a new speed using affinity laws, with annual energy difference for VFD screening.
Can I use this for a final design?
Use it for screening, diagnostics and opportunity sizing. Validate final design against measured plant data, OEM limits and applicable standards.