Cooling Tower Fan Affinity Calculator — VFD Speed, Airflow, Pressure & Power

Estimate cooling-tower fan airflow, pressure and power at a new speed using affinity laws, with annual energy difference for VFD screening.

Inputs

Live results

  • Speed ratio 0.8
  • New airflow 80,000
  • New pressure 160
  • New ideal power 15.36 kW
  • Annual energy difference 73.2 MWh

Formula

Q₂/Q₁=N₂/N₁; ΔP₂/ΔP₁=r²; P₂/P₁=r³.

Worked example

Reducing a 30 kW fan from 100% to 80% speed gives about 15.36 kW ideal affinity power.

Assumptions and limits

  • Affinity laws assume similar system/fan behavior and unchanged geometry.
  • Minimum tower airflow and thermal performance must be checked separately.

FAQs

What does this Cooling Tower Fan Affinity Calculator calculate?

Estimate cooling-tower fan airflow, pressure and power at a new speed using affinity laws, with annual energy difference for VFD screening.

Can I use this for a final design?

Use it for screening, diagnostics and opportunity sizing. Validate final design against measured plant data, OEM limits and applicable standards.

Why does the calculator show intermediate results?

Intermediate engineering quantities make bad inputs and unrealistic assumptions easier to spot before a decision is made.