Skip to main content

Find your next tool

MAXScanner Calculator

Extractor Fan & Range Hood Size Calculator

Airflow for a bathroom, shower, WC, utility or kitchen extractor fan or a range hood in l/s, m³/h and CFM: UK Part F, US ASHRAE and HVI, air changes, hob width or BTU, duct losses.

Live calculationWorking shown

Extractor fan and range hood sizing · UK, US and EU rules

The airflow your fan needs

Pick the rules and the room, then its size. The table compares building rules with rules of thumb, and the duct allowance turns the answer into the figure to look for on a fan.

Units
Room size

Floor area 5.0 m² · volume 12.0 m³

Duct from the fan to the outside

Airflow to size the fan for

26.7 l/s

96 m³/h · 57 cfm

Set by: Air changes

Legal minimum, UK Approved Document F: 15 l/s (54 m³/h, 32 cfm)

That is 8.0 air changes an hour in 12.0 m³.

Every method side by side
MethodRule appliedl/sm³/hcfmRole
UK Approved Document FTable 1.1: bathroom or shower room15 l/s54 m³/h32 cfmLegal minimum
US ASHRAE 62.2Table 5-1: bathroom or toilet room23.6 l/s85 m³/h50 cfmFor comparison
HVI bathroom rule1 cfm per ft² of floor (54 ft²)25.4 l/s91 m³/h54 cfmFor comparison
Air changes12.0 m³ × 8 an hour26.7 l/s96 m³/h57 cfmGoverns

If the fan runs all the time instead

UK continuous extract, high rate (Table 1.2): 8 l/s (29 m³/h, 17 cfm)

US continuous exhaust (Table 5-2): 9.4 l/s (34 m³/h, 20 cfm)

Duct allowance

26.7 l/s through 1 m of 100 mm duct: 17.4 Pa (0.07 in. w.c.) at an air speed of 3.4 m/s.

Counted as 5.57 m of straight duct: each bend adds 15 ft (4.57 m), as in the IRC duct table, and the outlet adds 4.57 m more.

Look for a fan whose curve gives 26.7 l/s (96 m³/h, 57 cfm) at 17.4 Pa.

On the box that is about 40.9 l/s (147 m³/h, 87 cfm) of free air for this fan type (straight-line curve down to 50 Pa).

More actions

Shared links reopen these inputs. Recent and saved calculations stay in this browser unless you clear site data.

Runs in your browser. Nothing you type is uploaded.

Minimum extract rates by room: UK and US

Code minimums for a fan that runs while the room is used, and for one that runs all the time, converted with 1 l/s = 3.6 m³/h = 2.119 cfm.

RoomUK, while in use (Table 1.1)UK, continuous high rate (Table 1.2)US, while in use (Table 5-1)US, continuous (Table 5-2)
Kitchen with a cooker hood30 l/s (108 m³/h)13 l/s (47 m³/h)100 cfm (47.2 l/s)5 air changes an hour
Kitchen without a hood (wall or ceiling fan)60 l/s (216 m³/h)13 l/s (47 m³/h)300 cfm (141.6 l/s) / 5 air changes an hour5 air changes an hour
Bathroom15 l/s (54 m³/h)8 l/s (29 m³/h)50 cfm (23.6 l/s)20 cfm (9.4 l/s)
Shower room15 l/s (54 m³/h)8 l/s (29 m³/h)50 cfm (23.6 l/s)20 cfm (9.4 l/s)
WC or toilet6 l/s (22 m³/h)6 l/s (22 m³/h)50 cfm (23.6 l/s)20 cfm (9.4 l/s)
Utility room30 l/s (108 m³/h)8 l/s (29 m³/h)nonenone

Worked examples

Each line is this calculator’s own result for the room described.

  • UK bathroom, 2.5 × 2 × 2.4 m (12.0 m³): Approved Document F asks for 15 l/s (54 m³/h), 8 air changes need 26.7 l/s (96 m³/h). Through 1 m of 100 mm duct with a wall flap (17.4 Pa) an axial fan should show about 40.9 l/s (147 m³/h) on the box.
  • Internal WC, 1.5 × 0.9 × 2.4 m (3.2 m³) with no outside wall: the 6 l/s of Table 1.1 is more than 4 air changes (3.6 l/s), and 8 air changes would be 7.2 l/s (26 m³/h).
  • UK kitchen without a hood, 3.5 × 3 × 2.4 m (25.2 m³): Table 1.1 asks for 60 l/s (216 m³/h), 10 air changes need 70 l/s (252 m³/h), so size for 70 l/s (252 m³/h).
  • US bathroom, 10 × 8 × 8 ft (80 ft²): HVI’s 1 cfm per ft² gives 80 cfm, above the 50 cfm (23.6 l/s) of ASHRAE 62.2.
  • US bathroom, 12 × 10 × 8 ft (120 ft²) with a toilet, a shower and a bath: over 100 ft², so HVI adds the fixtures to 150 cfm.
  • Kitchen of 4 × 3 × 2.5 m (30.0 m³) with a 60 cm induction hob and a wall hood: 10 air changes give 300 m³/h and the width rule 334 m³/h (92.9 l/s). Through 3 m of 150 mm duct with two bends and a flap (58.7 Pa) the hood should be rated about 392 m³/h (108.9 l/s).
  • US kitchen with a 30 in gas range of 40,000 Btu/h: the burners ask for 400 cfm and the width for 250 cfm. With 10 ft of 8 in duct, two elbows and a wall cap (55.3 Pa) the hood needs about 464 cfm of free air, over 400 cfm, so makeup air comes into play.

What the duct run does to the fan you need

Free-air rating needed to deliver 25 l/s (90 m³/h), with the assumed maximum pressures of 50 Pa for an axial fan and 150 Pa for a centrifugal one.

Duct runDuct pressureAxial fanCentrifugal fan
100 mm, 0.5 m, wall flap14.6 Pa35.3 l/s (127 m³/h)27.7 l/s (100 m³/h)
100 mm, 3 m, 2 bends, wall flap34.1 Pa78.8 l/s (284 m³/h)32.4 l/s (117 m³/h)
100 mm flexible, 3 m, 2 bends, wall flap66.3 Pacannot reach it44.8 l/s (161 m³/h)
125 mm, 3 m, 2 bends, wall flap12.0 Pa32.9 l/s (118 m³/h)27.2 l/s (98 m³/h)
125 mm, 6 m, 3 bends, roof terminal18.9 Pa40.2 l/s (145 m³/h)28.6 l/s (103 m³/h)

A wider duct cuts the loss far more than a stronger fan makes up for it, and flexible hose of the same length about doubles it.

Sources: GOV.UK (MHCLG), Approved Document F, Volume 1: Dwellings, 2021 edition (Tables 1.1 and 1.2, paragraphs 1.19–1.25, 1.48, 1.51, 1.76–1.80, 4.2); GOV.UK (MHCLG), Approved Document F, Volume 1: Dwellings, 2026 edition (takes effect 24 March 2027) (Tables 1.1 and 1.2); ASHRAE, Addendum e to ANSI/ASHRAE Standard 62.2-2022 (Tables 5-1 and 5-2, section 7.3); ICC (via UpCodes), International Residential Code 2021 and 2024, M1503.6 Makeup air required (M1503.6); ICC (via UpCodes), International Residential Code 2021, Chapter 15 Exhaust systems (M1503.3, Table M1504.2 note, M1505.3, Table M1505.4.4); Home Ventilating Institute, How much ventilation do I need? (Bathrooms, kitchens); Home Ventilating Institute, Bathroom ventilation (1 cfm per ft², about 8 air changes); Broan-NuTone, How much CFM do I need for my range or cook top? (1 cfm per 100 Btu); Agrarbildungszentrum Landsberg am Lech (Bezirk Oberbayern), Dunstabzugshaube: Auswahlkriterien und Einbauhinweise (Leistungskriterien, Abluftleitung, Zuluft); Neff, Optimale Höhe der Dunstabzugshaube (Luftwechsel); Verbraucherzentrale, Dunstabzugshauben: Darauf sollten Sie beim Kauf achten (Abluft, Umluft, Zuluft); ASHRAE, Handbook—Fundamentals, Duct Design: duct roughness (Galvanised steel 0.09 mm; flexible duct 1.0–4.6 mm). Rules read on 17 November 2026.

How the airflow is worked out

In England a bathroom or shower room fan must extract at least 15 l/s while the room is in use (54 m³/h, 32 cfm), a WC 6 l/s, a utility room 30 l/s, and a kitchen 30 l/s through a cooker hood ducted outside or 60 l/s without one (Approved Document F, Table 1.1). US rules ask for 50 cfm in a bathroom and 100 cfm from a vented range hood (ASHRAE 62.2), and HVI recommends 1 cfm per square foot of bathroom floor. Those are floors, not targets: a 2.5 × 2.0 m bathroom with a 2.4 m ceiling needs 26.7 l/s (96 m³/h) at 8 air changes an hour, and every metre of duct and every bend takes airflow away from the fan. This calculator puts the rules side by side, picks the one that governs, and turns it into the free-air figure to look for on the box.

How to use this calculator

1

Choose the rules you build under (United Kingdom, United States, Germany and Europe, or another country) and the room: kitchen with or without a hood, bathroom, shower room, WC or utility room.

2

Type the length, width and ceiling height, or the floor area and height, in metres or feet.

3

For a cooker hood, add the hob width and, for gas, the total burner output; tick island or recirculating where they apply.

4

Describe the duct: diameter, rigid or flexible, straight length, 90° bends, the outlet and the fan type.

5

Read the governing airflow in l/s, m³/h and CFM, then the pressure and free-air rating to compare with fan data sheets.

Where people use it

  • •Replacing a bathroom fan in England and checking that the new one still meets the 15 l/s of Approved Document F once its duct and wall flap are fitted.
  • •Choosing a range hood for a 30 in gas range in the US, where 40,000 Btu/h of burners asks for 400 cfm and the duct decides whether makeup air follows.
  • •Working out the m³/h for a cooker hood in a 30 m³ kitchen in Germany before comparing hood data sheets.

Example: a 2.5 × 2.0 m bathroom in England

The room is 2.5 × 2.0 × 2.4 m, so 12 m³. Approved Document F asks for 15 l/s; 8 air changes an hour need 12 × 8 ÷ 3.6 = 26.7 l/s (96 m³/h, 57 cfm), so 26.7 l/s governs. The fan blows through 1 m of 100 mm rigid duct to a wall outlet with a flap. Counted as 5.6 m of straight duct, that run costs 17.4 Pa at 26.7 l/s. An axial fan assumed to reach 50 Pa needs about 40.9 l/s (147 m³/h) free air to deliver it; a centrifugal fan assumed to reach 150 Pa needs about 30.2 l/s.

When to ask a ventilation engineer

  • •The figures are minimums and rules of thumb. Ask a ventilation engineer to design whole-house systems (continuous extract, MVHR), long or shared ducts, and any kitchen hood above about 400 cfm (680 m³/h).
  • •In England the airflow of a new fan or cooker hood has to be measured at commissioning and the result given to building control (Approved Document F, paragraphs 4.1, 4.2 and 4.9). This page does not replace that test.
  • •The duct allowance is an estimate: each bend counts as 15 ft (4.57 m) of duct, a wall flap as one more bend and a roof terminal as two, and the fan curve is taken as a straight line to an assumed maximum pressure. The fan’s own curve at your duct’s pressure is the real answer.
  • •A recirculating hood removes grease and smells but no moisture. It does not count as extract ventilation in England or as a vented hood under ASHRAE 62.2.
  • •Open-flued gas, oil or solid-fuel appliances can spill fumes into the room when a strong fan runs. In the UK follow Approved Document J, in the US check IRC M1503.6 on makeup air, and in Germany ask about a window contact switch.
  • •Germany’s standards for windowless bathrooms (DIN 18017-3) and whole-flat ventilation (DIN 1946-6) are paid documents, so their figures are not in this calculator, and California’s 2025 Energy Code sets its own range hood airflow or capture efficiency. Check those where they apply.

Frequently asked questions

What size extractor fan do I need for a bathroom?+

In England at least 15 l/s (54 m³/h) for a fan that runs while the room is used, or a high rate of 8 l/s for one that runs all the time (Approved Document F). US rules ask for 50 cfm, and HVI suggests 1 cfm per square foot up to 100 ft². For a 2.5 × 2.0 × 2.4 m bathroom, 8 air changes an hour come to 26.7 l/s (96 m³/h): size for that, then allow for the duct.

How many CFM do I need for a bathroom fan?+

HVI recommends 1 cfm per square foot of floor for bathrooms up to 100 ft² and never less than 50 cfm, so an 8 × 10 ft bathroom needs 80 cfm. Above 100 ft², add 50 cfm per toilet, shower and bath and 100 cfm per jetted tub: a 12 × 10 ft bathroom with all three needs 150 cfm.

What is the extraction rate for a kitchen?+

Approved Document F asks for 30 l/s (108 m³/h) from a cooker hood that is ducted outside and spans the hob, or 60 l/s (216 m³/h) from a kitchen fan without one. A 3.5 × 3.0 m kitchen with a 2.4 m ceiling needs 70 l/s (252 m³/h) at 10 air changes an hour.

How do I calculate CFM for a range hood?+

Take the larger of two rules of thumb: 100 cfm per foot of hood width against a wall or 150 over an island (HVI), and for gas 1 cfm per 100 Btu/h of total burner output (Broan-NuTone). A 30 in gas range with 40,000 Btu/h asks for 400 cfm. The US code minimum for a vented hood is 100 cfm (ASHRAE 62.2).

How many m³/h does a cooker hood need?+

Multiply the kitchen volume by the air changes you want: a 4 × 3 m kitchen with a 2.5 m ceiling holds 30 m³, so 10 air changes an hour need 300 m³/h. A 60 cm hood against a wall asks for 334 m³/h by the width rule, and 3 m of 150 mm duct with two bends and a flap raises the rating to look for to about 392 m³/h.

Does a 400 CFM range hood need makeup air?+

Under the IRC (M1503.6 in the 2021 and 2024 editions), makeup air is needed when an exhaust system can move more than 400 cfm and a fuel-burning appliance that is neither direct-vent nor power-vented sits inside the home’s air barrier. A hood rated exactly 400 cfm is not over the limit, but one that must be rated about 464 cfm to deliver 400 cfm through 10 ft of 8 in duct with two elbows and a wall cap is. Local codes can be stricter.

Do bends and duct length reduce extractor fan performance?+

Yes. The IRC duct table counts every elbow as 15 ft (4.57 m) of extra duct, and flexible hose loses about twice as much as smooth pipe. At 25 l/s, 3 m of 100 mm duct with two bends and a wall flap costs 34.1 Pa, which an axial fan could only beat with about 78.8 l/s of free-air rating. A 125 mm duct cuts the same run to 12.0 Pa.

Can a recirculating cooker hood replace an extractor fan?+

Not as the kitchen’s ventilation in England: Approved Document F says a recirculating hood on its own does not comply, so the kitchen still needs 60 l/s of extract to the outside. In the US a listed ductless hood is allowed only where the kitchen is ventilated in another way.

Semantic next steps

Continue the calculation

These links move to a different input, formula or project stage rather than a keyword variation of this page.

Free publisher widget

Put this calculator on your website

Give readers the live calculator without rebuilding the math. Copy the responsive embed in one click, or customize width, height, border and corner radius before publishing. The branded MAXScanner attribution stays visible.

Preview

Calculator embed HTML

Paste this code into your page. Focus the code box to select it manually.

Keep the result connected to the real job

MAXScanner keeps the formula and assumptions beside the result so you can verify the number before using it in a drawing, estimate, specification, worksheet or document. Where a supplier, manufacturer, drawing or applicable standard owns a requirement, that source remains authoritative.