Formula & worked example
Q=ρ·cp·Vdot·ΔT·(1−εHRV).
500 CFM outdoor air with 20 K ΔT is about 5.7 kW sensible load before recovery at standard density.
Heating & HVAC engineering calculator · Updated Sep 17, 2026
Calculate sensible ventilation heating load from airflow and temperature difference, including heat-recovery effectiveness.
Q=ρ·cp·Vdot·ΔT·(1−εHRV).
500 CFM outdoor air with 20 K ΔT is about 5.7 kW sensible load before recovery at standard density.
Calculate sensible ventilation heating load from airflow and temperature difference, including heat-recovery effectiveness.
Inputs state their unit basis and results include practical SI and US customary equivalents where useful, so the calculation can be checked against field data and equipment schedules.
Use it for transparent first-pass sizing and engineering cross-checks. Final selections should use measured conditions, manufacturer performance data and applicable codes or design standards.