Ventilation Heat Loss Calculator — Airflow, ΔT & Heat Recovery

Calculate sensible ventilation heating load from airflow and temperature difference, including heat-recovery effectiveness.

Inputs

Live result

Temperature difference 20 K
Gross sensible load 5.6973496 kW
Recovered heat 3.9881447 kW
Net ventilation load 1.7092049 kW (5,832.0491 BTU/h)

Formula & worked example

Q=ρ·cp·Vdot·ΔT·(1−εHRV).

500 CFM outdoor air with 20 K ΔT is about 5.7 kW sensible load before recovery at standard density.

Assumptions & limits

  • Sensible load only; latent moisture load is separate.
  • Density and heat capacity are explicit inputs.

Frequently asked questions

What does this Ventilation Heat Loss Calculator calculate?

Calculate sensible ventilation heating load from airflow and temperature difference, including heat-recovery effectiveness.

What units are supported?

Inputs state their unit basis and results include practical SI and US customary equivalents where useful, so the calculation can be checked against field data and equipment schedules.

Can I use this for final equipment selection?

Use it for transparent first-pass sizing and engineering cross-checks. Final selections should use measured conditions, manufacturer performance data and applicable codes or design standards.