Heating Load Calculator — U-Value, Area, Infiltration & Heater Size

Estimate design heating load from envelope UA loss plus infiltration, with watts, BTU/h, kW and a configurable sizing margin.

Inputs

Live result

Temperature difference 25 K
Envelope loss 1.35 kW
Infiltration/air load 1.4243374 kW
Block heating load 2.7743374 kW (9,466.4322 BTU/h)
Design output with margin 3.0517711 kW

Formula & worked example

Q=Σ(U·A·ΔT)+ρ·cp·Vdot·ΔT; Qdesign=Q·(1+margin).

A 120 m² envelope at U=0.45 W/m²K and 25 K temperature difference loses 1.35 kW by transmission before infiltration.

Assumptions & limits

  • Uses a lumped envelope U-value and area for a transparent block-load estimate.
  • Solar/internal gains and thermal bridges are not silently credited.

Frequently asked questions

What does this Heating Load Calculator calculate?

Estimate design heating load from envelope UA loss plus infiltration, with watts, BTU/h, kW and a configurable sizing margin.

What units are supported?

Inputs state their unit basis and results include practical SI and US customary equivalents where useful, so the calculation can be checked against field data and equipment schedules.

Can I use this for final equipment selection?

Use it for transparent first-pass sizing and engineering cross-checks. Final selections should use measured conditions, manufacturer performance data and applicable codes or design standards.