Formula & worked example
Tmix=(Qoa·Toa+Qra·Tra)/(Qoa+Qra); OA%=Qoa/(Qoa+Qra)·100; OA%target=(Ttarget−Tra)/(Toa−Tra)·100.
1,000 CFM outdoor air at 35°C mixed with 4,000 CFM return air at 24°C gives 26.2°C mixed air and 20% outside air.
HVAC engineering calculator · Updated Sep 17, 2026
Mix outside and return air by airflow, calculate mixed-air temperature and outside-air fraction, or reverse-solve the outside-air percentage needed for a target mixed-air temperature.
Tmix=(Qoa·Toa+Qra·Tra)/(Qoa+Qra); OA%=Qoa/(Qoa+Qra)·100; OA%target=(Ttarget−Tra)/(Toa−Tra)·100.
1,000 CFM outdoor air at 35°C mixed with 4,000 CFM return air at 24°C gives 26.2°C mixed air and 20% outside air.
Mix outside and return air by airflow, calculate mixed-air temperature and outside-air fraction, or reverse-solve the outside-air percentage needed for a target mixed-air temperature.
HVAC results depend on air properties, measured conditions and design conventions. MAXScanner exposes the governing assumptions so the result can be checked instead of hiding them behind a single number.
No. Use it for transparent sizing and cross-checking, then verify final selections against measured conditions, equipment data and applicable design standards.