Formula & worked example
Tmix=(Qoa·Toa+Qra·Tra)/(Qoa+Qra); OA%=Qoa/(Qoa+Qra)·100; OA%target=(Ttarget−Tra)/(Toa−Tra)·100.
1,000 CFM outdoor air at 35°C mixed with 4,000 CFM return air at 24°C gives 26.2°C mixed air and 20% outside air.
Help improve MAXScanner?
Optional usage analytics can tell us which tools and workflows are useful. File names, document contents, typed values, search queries and workflow tokens are not sent.
HVAC engineering calculator · Updated Sep 17, 2026
Mix outside and return air by airflow, calculate mixed-air temperature and outside-air fraction, or reverse-solve the outside-air percentage needed for a target mixed-air temperature.
Tmix=(Qoa·Toa+Qra·Tra)/(Qoa+Qra); OA%=Qoa/(Qoa+Qra)·100; OA%target=(Ttarget−Tra)/(Toa−Tra)·100.
1,000 CFM outdoor air at 35°C mixed with 4,000 CFM return air at 24°C gives 26.2°C mixed air and 20% outside air.
Mix outside and return air by airflow, calculate mixed-air temperature and outside-air fraction, or reverse-solve the outside-air percentage needed for a target mixed-air temperature.
HVAC results depend on air properties, measured conditions and design conventions. MAXScanner exposes the governing assumptions so the result can be checked instead of hiding them behind a single number.
No. Use it for transparent sizing and cross-checking, then verify final selections against measured conditions, equipment data and applicable design standards.