How to use this calculator
- Enter measured or design values using the units shown beside each field.
- Review the live results and the substituted calculation steps before using the estimate.
- Check the assumptions below, then continue to a related calculator when the next engineering decision needs another model.
Worked example
A 20 L/s bypass at 30 m head wastes about 5.88 kW hydraulically before pump and motor efficiency correction.
Assumptions and limits
- Treats bypass flow and head as steady screening values.
- Verify minimum-flow protection, pump curve and control requirements before reducing recirculation.