How to use this calculator
- Enter measured or design values using the units shown beside each field.
- Review the live results and the substituted calculation steps before using the estimate.
- Check the assumptions below, then continue to a related calculator when the next engineering decision needs another model.
Worked example
A pump requiring 40 L/s minimum with 25 L/s process demand needs 15 L/s recirculation.
Assumptions and limits
- Minimum stable/thermal flow must come from the pump OEM or validated engineering basis.
- A bypass protects the pump but can waste energy and heat the fluid.
- The input-equivalent kW is a screening conversion using the entered efficiency, not a full pump/system-curve model.