How to use this calculator
- Enter measured or design values using the units shown beside each field.
- Review the live results and the substituted calculation steps before using the estimate.
- Check the assumptions below, then continue to a related calculator when the next engineering decision needs another model.
Worked example
Feedwater conductivity of 200 µS/cm and a 2,000 µS/cm boiler setpoint gives 10 cycles. At 10,000 kg/h steam, ideal continuous blowdown is about 1,111 kg/h; the calculator also annualizes hot-water and treatment losses.
Assumptions and limits
- Compare conductivity on the same temperature-compensated basis, commonly 25°C.
- Conductivity is a practical dissolved-solids concentration proxy, not a universal fixed TDS conversion; calibrate against site chemistry.
- Assumes dissolved solids leave mainly with blowdown and steam carryover is negligible.
- Use the boiler OEM and water-treatment specialist limits for the actual conductivity setpoint.