How to use this calculator
- Enter measured or design values using the units shown beside each field.
- Review the live results and the substituted calculation steps before using the estimate.
- Check the assumptions below, then continue to a related calculator when the next engineering decision needs another model.
Worked example
A 10,000 kg/h feedwater stream heated from 30°C to 90°C needs about 698 kW of sensible heating duty when Cp is 4.186 kJ/kg·K.
Assumptions and limits
- Uses a constant water Cp entered by the user.
- Steam equivalent is an energy screen; final heater design requires steam-table enthalpies, drain and subcooling checks.