Skip to main content

Find your next tool

Electrical & Engineering Calculators

Cable Pulling Tension Calculator — Route Builder, Sidewall Pressure & Max Tension

Pulling tension adds cable weight × friction × length on each straight run and is multiplied by e^(f × θ) at every bend, so bend order matters. Build the route section by section, compare both pull directions and check sidewall pressure and the allowable tension.

Live calculationWorking shown

Editable live calculator

Change any input — the result updates immediately

No hidden assumptions. Inputs, units and the working stay visible so you can check the calculation.

Route in pull order (ft)

Enter the sections in pull order, from where the cable is fed in to the puller. A bend takes its total angle and radius; an incline takes its slope angle from level.

  1. Section 1
  2. Section 2
  3. Section 3
  4. Section 4

Calculated result

Pull reverse: 115.9 lbf final tension (forward 243.6 lbf)

Forward pull (cable fed in at section 1): 243.6 lbf final tension, 24.8 lbf/ft highest sidewall pressure

Reverse pull (cable fed in at section 4): 115.9 lbf final tension, 4.2 lbf/ft highest sidewall pressure

Reverse is the lower-tension direction: 127.6 lbf less at its highest point (52% lower).

Weight correction factor w = 1.0352 (three cables, triangular; d ÷ (D − d) = 0.2584).

Jam ratio D ÷ d = 4.87: very small probability of jamming (Cerrowire bands; the risk peaks between 2.8 and 3.0).

Allowable pulling tension: 5,078.4 lbf (pulling eye, copper conductors).

Highest tension: forward 5%, reverse 2% of the allowable.

Highest sidewall pressure: forward 5%, reverse 1% of the 500 lbf/ft limit.

Total bends between pull points: 90° (the NEC allows up to 360° for conduit).

Tension leaving each section

SectionForward tensionForward sidewallReverse tensionReverse sidewall
1. Straight 150 ft91.3 lbf–115.9 lbf–
2. Bend 90°, R 3 ft143.9 lbf24.8 lbf/ft24.6 lbf4.2 lbf/ft
3. Uphill 40 ft at 30°207 lbf–15.6 lbf–
4. Straight 60 ft243.6 lbf–36.5 lbf–
Show the working
  1. 1. Cable weight W = 2.1 lb/ft; friction f = 0.28; w × f = 0.2898; back tension at the feed end 0 lbf.
  2. 2. Forward pull, section 1 to section 4:
  3. 3. Section 1, straight 150 ft: 0 lbf + 1.0352 × 0.28 × 2.1 lb/ft × 150 ft = 91.3 lbf.
  4. 4. Section 2, 90° bend: 91.3 lbf × e^(0.2898 × 1.5708 rad) = 143.9 lbf; sidewall pressure = 1.0352 × 143.9 lbf ÷ (2 × 3 ft) = 24.8 lbf/ft.
  5. 5. Section 3, uphill 40 ft at 30°: 143.9 lbf + 2.1 lb/ft × 40 ft × (sin 30° + 0.2898 × cos 30°) = 207 lbf.
  6. 6. Section 4, straight 60 ft: 207 lbf + 1.0352 × 0.28 × 2.1 lb/ft × 60 ft = 243.6 lbf.
  7. 7. Reverse pull, section 4 to section 1 (uphill and downhill swap):
  8. 8. Section 4, straight 60 ft: 0 lbf + 1.0352 × 0.28 × 2.1 lb/ft × 60 ft = 36.5 lbf.
  9. 9. Section 3, downhill 40 ft at 30°: 36.5 lbf − 2.1 lb/ft × 40 ft × (sin 30° − 0.2898 × cos 30°) = 15.6 lbf.
  10. 10. Section 2, 90° bend: 15.6 lbf × e^(0.2898 × 1.5708 rad) = 24.6 lbf; sidewall pressure = 1.0352 × 24.6 lbf ÷ (2 × 3 ft) = 4.2 lbf/ft.
  11. 11. Section 1, straight 150 ft: 24.6 lbf + 1.0352 × 0.28 × 2.1 lb/ft × 150 ft = 115.9 lbf.
  12. 12. Conductor limit = 0.008 lb/cmil × 3 × 211,600 cmil = 5,078.4 lbf.
  13. 13. Pulling-eye cap for two or more conductors: 10,000 lbf; allowable = 5,078.4 lbf.

Estimate only. Friction, the weight correction factor and the published limits are planning values: follow the cable manufacturer's maximum pulling tension, sidewall pressure and minimum bending radius for the cable you install. Vertical bends are treated as horizontal bends, which ignores the cable weight inside the bend.

More actions

Shared links reopen these inputs. Recent and saved calculations stay in this browser unless you clear site data.

The calculation, without hidden assumptions

Cable pulling tension builds up one section at a time. A level straight run adds cable weight × friction × length, an uphill run also adds the weight component of the slope, and a bend multiplies whatever tension enters it by e^(f × θ). Because bends multiply, the same route pulled from the other end can need far less force. Enter the route in pull order, one row per straight, incline or bend, and the calculator works out both directions, the sidewall pressure leaving every bend, the jam ratio for three cables, and the allowable tension from the conductors (0.008 lb per circular mil for copper on a pulling eye) or from the limit your cable manufacturer gives.

How to use this calculator

1

Choose feet or metres, then add one row per section in the order the cable travels: level straight runs, inclines (uphill or downhill as seen from the feed end) and bends with their angle and radius.

2

Enter the total weight per length of everything pulled together, pick how the cables lie in the conduit, and pick a friction value from the presets or type your own. For three single cables, give the conduit inside diameter and the cable outside diameter so the weight correction factor and jam ratio come from your sizes.

3

Set the allowable tension from the conductors (metal, size, number of current-carrying conductors and pulling eye or basket grip) or type the figure from the cable data sheet, and enter the sidewall pressure limit you work to.

4

Read the recommended direction, check the per-section table for the bend with the highest sidewall pressure, and download the route as a CSV for the pull plan.

Where people use it

  • •Choosing which end of a feeder run to set up the reel and which end the puller
  • •Checking a multi-bend conduit run against the cable maker's tension and sidewall pressure limits before the pull
  • •Seeing whether an extra pull point, larger sweeps or a better lubricant brings an over-limit pull back inside the limits
  • •Recording the route, tensions and limits for a pull plan or a submittal as a CSV

Worked example: three 4/0 copper cables, 4 sections

Three 4/0 AWG copper single conductors weighing 2.1 lb/ft together, 0.63 in OD, triangular in 3 in rigid conduit (3.068 in ID), lubricated (f = 0.28). Route in pull order: 150 ft straight, a 90° bend with a 3 ft radius, 40 ft uphill at 30°, then 60 ft straight. The weight correction factor is 1.0352, so w × f = 0.2898. Pulled forward, the tension is 91.3 lbf before the bend, 143.9 lbf after it (sidewall pressure 24.8 lbf/ft), 207 lbf at the top of the incline and 243.6 lbf at the puller. Pulled in reverse, the bend comes late and the incline runs downhill, so the final tension is 115.9 lbf: 52 % less. The conductor limit on a pulling eye is 0.008 × 3 × 211,600 cmil = 5,078.4 lbf, so either direction is far inside it, and the jam ratio of 4.87 carries a very small risk of jamming.

What the result does not assume

  • •An estimate for planning. The cable manufacturer's maximum pulling tension, sidewall pressure and minimum bending radius govern, and so does the rating of the puller, rope and grip.
  • •Friction presets are typical published values for lubricated pulls, not standards: 0.24 (PVC) and 0.28 (steel or aluminum conduit) for THHN/XHHW from the Cerrowire Installation Information sheet; 0.35 (PVC), 0.25 (polyethylene) and a conservative 0.50 from the ShawFlex Cable Handling, Storage and Installation Guide. A stopped pull restarts at the higher static friction.
  • •Vertical bends are entered as bends and use the horizontal-bend equation, which leaves out the cable weight inside the bend. Where a riser or a dip has little tension entering it, use pull-planning software instead.
  • •The allowable tension follows Service Wire's Maximum Pulling Tensions sheet (pulling eye k × n × A, 6,000 lb and 10,000 lb caps, basket grip at most 1,000 lb) and Cerrowire's 20 % reduction above three conductors. Leave neutral and grounding conductors out of n. Service Wire also advises 20 % to 40 % less when several single conductors are pulled in parallel, because they do not share the load evenly.
  • •Sidewall pressure and weight correction formulas are those of Okonite Technical News Edition 005 for three equal single cables; Okonite measures R as the inside radius of the bend. Its limits: 300 lb/ft for one cable of 8 AWG or smaller, 500 lb/ft for one larger cable, 1,000 lb/ft for two or more larger cables checked with T ÷ R, and 500 lb/ft whenever the triangular or cradled form is used.
  • •Conduit fill, clearance, ampacity, pull-box size and lubricant compatibility are separate checks.

Frequently asked questions

How do you calculate cable pulling tension?+

Split the route into sections and work from the feed end to the puller. A level straight run adds weight per foot × friction coefficient × length (times the weight correction factor for three cables). A bend multiplies the tension entering it by e^(f × θ), with θ in radians: about 1.55 for a 90° bend at f = 0.28. The tension leaving the last section is the pulling tension.

What is the maximum pulling tension of a cable?+

With a pulling eye on the conductors, a common rule is 0.008 lb per circular mil for copper and 0.006 for aluminum, times the number of conductors: three 4/0 copper conductors (211,600 cmil each) allow 5,078 lb. Service Wire caps the result at 6,000 lb for one conductor and 10,000 lb for more, and a basket grip at 1,000 lb. The manufacturer's figure for your cable takes precedence.

Which end of the run should I pull from?+

Usually the end that puts the bends near the feed, because a bend multiplies the tension that has already built up. In the worked example, pulling from the other end cuts the final tension from 243.6 lbf to 115.9 lbf. The calculator runs both directions and recommends the lower one that stays within your limits.

What is sidewall pressure and what limit should I use?+

It is the force per foot of bend radius with which the cable is pressed against the inside of a bend: T ÷ R for one cable. Okonite suggests 500 lb/ft for one power cable larger than 8 AWG and for any three-cable triangular or cradled check, and 300 lb/ft for 8 AWG and smaller. Use the cable manufacturer's value when it gives one.

What coefficient of friction should I use for cable pulling?+

With pulling lubricant, Cerrowire lists 0.24 for THHN in PVC conduit and 0.28 in steel or aluminum conduit, and ShawFlex lists 0.35 for PVC-jacketed cable in PVC conduit and 0.25 in polyethylene duct. When the conditions are unknown, ShawFlex suggests a conservative 0.50.

What is the jam ratio?+

The conduit inside diameter divided by the cable outside diameter, for three or more single cables. Cerrowire rates the risk of the cables wedging side by side as significant between 2.8 and 3.0, moderate from 2.6 to 2.8 and from 3.0 to 3.1, and very small below 2.3 or from 3.2 up. Use measured cable diameters, since real ones differ from catalog values.

Semantic next steps

Continue the calculation

These links move to a different input, formula or project stage rather than a keyword variation of this page.

Electrical & Engineering Calculators

Voltage Drop Calculator — Cable Drop, Max Length, Current & Minimum Area

Calculate voltage drop for copper or aluminum conductors, or reverse-solve maximum cable length, maximum current and minimum mm² area for a chosen drop target across DC, single-phase and balanced three-phase circuits.

Conduit Fill Calculator — Wire & Cable Raceway Fill

Calculate conduit fill from actual cable outside diameters and raceway inside diameter, check 53/31/40% conductor-count limits or a custom limit, and reverse-solve minimum ideal ID.

Cable Reel & Drum Capacity Calculator (m or ft)

An 800 mm drum (300 mm barrel, 450 mm wide, 25 mm freeboard) holds about 382.73 m of 20 mm cable at 90% packing and 80% fill. Enter your drum for m or ft.

Copper Wire Weight Calculator: kg/m, AWG & kcmil

Copper weighs 8.89 g per metre for each mm²: 2.5 mm² is 22.2 g/m and 1 kg of it is 45 m. Enter mm², AWG, kcmil or diameter, solid or stranded, any number of cores.

Pull Box Sizing Calculator — NEC 314.28 Straight, Angle & U Pulls

Calculate minimum pull-box and junction-box dimensions for 4 AWG and larger conductors using NEC 314.28 straight-pull, angle/U-pull and same-conductor raceway-spacing rules.

Conduit Offset Calculator — Bend Spacing, Shrink & Marks

Calculate equal-angle conduit offset bend spacing and published field shrink from Greenlee-style multiplier constants, with optional bend-mark and available-length checks.

Ampacity Derating Calculator — Temp & Conductors

Apply ambient-temperature correction and current-carrying-conductor adjustment to an entered starting ampacity, then compare an optional terminal ceiling and load.

Wireway Fill Calculator — 20% Fill & >30 Conductor Check

Calculate metal or nonmetallic wireway conductor fill against the 20% interior-area rule, minimum required area, >30 current-carrying-conductor flag and optional splice/tap point check.

More in this calculator collection

Browse nearby calculators in the same topic cluster so related pages reinforce each other instead of sitting as isolated URLs.

Free publisher widget

Put this calculator on your website

Give readers the live calculator without rebuilding the math. Copy the responsive embed in one click, or customize width, height, border and corner radius before publishing. The branded MAXScanner attribution stays visible.

Preview

Calculator embed HTML

Paste this code into your page. Focus the code box to select it manually.

Keep the result connected to the real job

MAXScanner keeps the formula and assumptions beside the result so you can verify the number before using it in a drawing, estimate, specification, worksheet or document. Where a supplier, manufacturer, drawing or applicable standard owns a requirement, that source remains authoritative.