Plant engineering calculator · Updated 17 September 2026
Condensate Receiver Level Band Calculator — Pump Cycle Volume & Runtime
Calculate receiver volume between pump start/stop levels, fill time, pump-out time and approximate cycles per hour from return and pump rates.
Inputs
Live results
- Cycle-band volume 0.6 m³
- Fill time 6 min
- Pump-out time 4 min
- Approx cycles/hour 6
Formula and method
Vband=Vtank×(high−low); fill=Vband/Qreturn; pumpout=Vband/(Qpump−Qreturn).
Worked example
A 2 m³ receiver with a 30% level band stores 0.6 m³ per cycle.
Engineering assumptions and limits
- Pump capacity must exceed return flow during pump-out.
- Linear level-volume assumption should be replaced by vessel calibration when needed.
Frequently asked questions
What does this Condensate Receiver Level Band Calculator calculate?
Calculate receiver volume between pump start/stop levels, fill time, pump-out time and approximate cycles per hour from return and pump rates.
Can I use this for final equipment selection?
Use it for transparent engineering screening. Final selection must be checked against vendor curves, operating envelopes, applicable standards and site measurements.