Glycol Expansion Calculator — Closed-Loop Expansion & Tank Acceptance

Estimate glycol-loop thermal expansion and ideal diaphragm-tank volume from system volume, cold/hot fluid density, fill pressure, relief pressure and design margin.

Inputs

Live result

Fluid expansion 29.70297 L
Expansion fraction 2.970297%
Pressure acceptance 37.376191%
Ideal tank volume 79.470297 L
Tank with margin 87.417327 L

Formula & worked example

Ve=Vs(ρcold/ρhot−1); Vtank=Ve/[1−Pfill,abs/Prelief,abs].

A 1,000 L glycol loop dropping from 1040 to 1010 kg/m³ expands about 29.7 L before pressure acceptance.

Assumptions & limits

  • Use glycol-mixture densities at actual cold/hot temperatures.
  • Manufacturer precharge and code sizing govern final tank selection.