Formula & worked example
Ve=Vs(ρcold/ρhot−1); Vtank=Ve/[1−Pfill,abs/Prelief,abs].
A 500 L loop expanding 2.5% creates 12.5 L expansion volume before pressure acceptance is applied.
HVAC design calculator · Updated Sep 17, 2026
Estimate closed-loop hydronic expansion-tank acceptance and nominal tank volume from system water volume, cold/hot density, fill pressure and relief pressure.
Ve=Vs(ρcold/ρhot−1); Vtank=Ve/[1−Pfill,abs/Prelief,abs].
A 500 L loop expanding 2.5% creates 12.5 L expansion volume before pressure acceptance is applied.
Estimate closed-loop hydronic expansion-tank acceptance and nominal tank volume from system water volume, cold/hot density, fill pressure and relief pressure.
Use the result as a transparent engineering cross-check. Confirm final selections against measured design conditions, manufacturer data, applicable standards and local code.
HVAC shortcuts can look precise while hiding density, efficiency, free-area or pressure assumptions. MAXScanner keeps the governing inputs visible so the result can be audited.