Formula & worked example
Ve=Vs(ρcold/ρhot−1); Vtank=Ve/[1−Pfill,abs/Prelief,abs].
A 500 L loop expanding 2.5% creates 12.5 L expansion volume before pressure acceptance is applied.
Help improve MAXScanner?
Optional usage analytics can tell us which tools and workflows are useful. File names, document contents, typed values, search queries and workflow tokens are not sent.
HVAC design calculator · Updated Sep 17, 2026
Estimate closed-loop hydronic expansion-tank acceptance and nominal tank volume from system water volume, cold/hot density, fill pressure and relief pressure.
Ve=Vs(ρcold/ρhot−1); Vtank=Ve/[1−Pfill,abs/Prelief,abs].
A 500 L loop expanding 2.5% creates 12.5 L expansion volume before pressure acceptance is applied.
Estimate closed-loop hydronic expansion-tank acceptance and nominal tank volume from system water volume, cold/hot density, fill pressure and relief pressure.
Use the result as a transparent engineering cross-check. Confirm final selections against measured design conditions, manufacturer data, applicable standards and local code.
HVAC shortcuts can look precise while hiding density, efficiency, free-area or pressure assumptions. MAXScanner keeps the governing inputs visible so the result can be audited.