How do I calculate three-phase motor current?
Convert shaft power to electrical input using efficiency, then divide by √3 × line voltage × power factor.
MAXScanner electrical calculator
Estimate single-phase or three-phase AC motor full-load current from shaft power, voltage, power factor and efficiency, with input kW, apparent kVA and adjustable starting-current context.
Calculated running current (theoretical)
14.151 A
Substituted calculation
I = (7.5 kW × 1000 W/kW ÷ 0.9) ÷ (√3 × 400 V × 0.85) = 14.151 A
Calculated current is not a code-table FLC or a nameplate value. Use the motor nameplate and applicable electrical standard for final conductor, overload, starter and protective-device selection.
3φ: I = Pshaft ÷ (√3 × V × PF × η); 1φ: I = Pshaft ÷ (V × PF × η).
A 7.5 kW three-phase motor at 400 V, 0.85 PF and 90% efficiency draws about 14.15 A at rated shaft output.
Last updated: 2026-09-16
Convert shaft power to electrical input using efficiency, then divide by √3 × line voltage × power factor.
A less-efficient motor needs more electrical input power to deliver the same shaft output, so line current increases.
Do not treat this estimate as a final protection setting. Use the motor nameplate and the rules in the electrical standard that applies to the installation.