Motor Current Calculator — kW/HP to Full-Load Amps

Estimate single-phase or three-phase AC motor full-load current from shaft power, voltage, power factor and efficiency, with input kW, apparent kVA and adjustable starting-current context.

Estimated full-load current

14.151 A

Electrical input: 8.333 kW

Apparent power: 9.804 kVA

Starting-current estimate at 6×: 84.9 A

Use the motor nameplate and applicable electrical code for final design and protection settings.

Formula and worked example

3φ: I = Pshaft ÷ (√3 × V × PF × η); 1φ: I = Pshaft ÷ (V × PF × η).

A 7.5 kW three-phase motor at 400 V, 0.85 PF and 90% efficiency draws about 14.15 A at rated shaft output.

What this calculation assumes

  • Motor kW or horsepower is treated as mechanical shaft output; electrical input power is higher by the inverse of efficiency.
  • The result is an engineering estimate. Motor nameplate current and the applicable electrical standard govern final cable, overload, starter and protective-device selection.
  • Starting current is shown only from the multiplier you enter; actual inrush depends on the motor and starting method.

Last updated: 2026-09-16

Frequently asked questions

How do I calculate three-phase motor current?

Convert shaft power to electrical input using efficiency, then divide by √3 × line voltage × power factor.

Why is calculated motor current higher when efficiency is lower?

A less-efficient motor needs more electrical input power to deliver the same shaft output, so line current increases.

Should I size a breaker from this calculated current?

Do not treat this estimate as a final protection setting. Use the motor nameplate and the rules in the electrical standard that applies to the installation.