How do I calculate three-phase motor current?
Convert shaft power to electrical input using efficiency, then divide by √3 × line voltage × power factor.
Help improve MAXScanner?
Optional usage analytics can tell us which tools and workflows are useful. File names, document contents, typed values, search queries and workflow tokens are not sent.
MAXScanner electrical calculator
Estimate single-phase or three-phase AC motor full-load current from shaft power, voltage, power factor and efficiency, with input kW, apparent kVA and adjustable starting-current context.
Estimated full-load current
14.151 A
Electrical input: 8.333 kW
Apparent power: 9.804 kVA
Starting-current estimate at 6×: 84.9 A
Use the motor nameplate and applicable electrical code for final design and protection settings.
3φ: I = Pshaft ÷ (√3 × V × PF × η); 1φ: I = Pshaft ÷ (V × PF × η).
A 7.5 kW three-phase motor at 400 V, 0.85 PF and 90% efficiency draws about 14.15 A at rated shaft output.
Last updated: 2026-09-16
Convert shaft power to electrical input using efficiency, then divide by √3 × line voltage × power factor.
A less-efficient motor needs more electrical input power to deliver the same shaft output, so line current increases.
Do not treat this estimate as a final protection setting. Use the motor nameplate and the rules in the electrical standard that applies to the installation.