Can target power factor be lower than initial?
For correction sizing here, target PF must be greater than the initial PF and no more than 1.
Help improve MAXScanner?
Optional usage analytics can tell us which tools and workflows are useful. File names, document contents, typed values, search queries and workflow tokens are not sent.
MAXScanner calculator
Calculate ideal capacitor reactive power needed to move a real-power load from an initial to a target displacement power factor.
Result
Check inputs
Qc(kVAR)=P(kW)×[tan(acos(PF1))−tan(acos(PF2))].
100 kW from PF 0.80 to 0.95 requires about 42.13 kVAR in the ideal sinusoidal displacement-PF model.
Last updated: 2026-09-16
For correction sizing here, target PF must be greater than the initial PF and no more than 1.
No. It is an ideal reactive-power target, not a complete bank design.