Transformer kVA Calculator — Single & Three Phase Load Sizing

Calculate load kVA from voltage and current for single or balanced three-phase systems, then apply an explicit spare-capacity percentage.

Result

83.138 kVA

69.282 kVA calculated load

Includes 20% entered spare capacity · balanced 3φ VLL formula.

Formula and worked example

1φ kVA=V×I/1000; balanced 3φ kVA=√3×VLL×I/1000; planned kVA=load kVA×(1+spare%).

400 V, 100 A balanced three-phase is about 69.28 kVA; 20% entered spare capacity gives 83.14 kVA planning load.

Assumptions

  • Three-phase voltage is line-to-line and load is balanced.
  • This does not select a standard transformer or protection settings.

Last updated: 2026-09-16

Frequently asked questions

Why does three phase use √3?

The balanced line-to-line three-phase apparent-power relationship includes √3.

Is spare capacity mandatory?

No. It is an explicit planning input, not a universal requirement.