Roof Snow Load Calculator: Weight and Design Load

How heavy is the snow on your roof: depth × density for fresh, settled or wet snow and ice, or a bucket sample, in kg/m², kN/m², psf and tonnes. Design load by ASCE 7-16, NBC 2020, Eurocode or Japan.

Live calculationWorking shown

Snow load · roof weight and design codes

How heavy is the snow on your roof?

Describe the roof and the snow, then compare the load with the design value from your plans or a building code.

What do you want to know?
Units
Roof

Codes and this result use the footprint. Sizes taken along the rafters are converted with the pitch.

Pitch 26.6° · 6.00:12 · 50.0 %

How do you know the snow?
Snow layers, top first

12.7 lb/ft³

Measure straight down where you can see the roof from a safe place, for example against a chimney. Snow on the ground is not the same depth as on the roof.

Compare with a design snow load

The roof snow load from the building’s structural drawings or calculation (per m² or ft² of footprint, before load factors), or the code result.

Snow load on the roof

12.73 psf

62.16 kg/m² · 0.61 kN/m² · 12.73 psf

Average density 204 kg/m³ (12.7 lb/ft³) over 12.0 in.

Total weight on the roof

6,930 kg · 6.93 t · 15,278 lb

Footprint 1,200.0 ft², roof surface 1,341.6 ft².

Spread over the sloped roofing: 11.39 lb on each ft².

This compares two numbers. It is not a structural check and cannot tell you that the roof is safe.

More actions

Shared links reopen these inputs. Recent and saved calculations stay in this browser unless you clear site data.

Runs in your browser. Nothing you type is uploaded.

How much snow weighs, kind by kind

Densities from Eurocode 1 (EN 1991-1-3, Annex E) and FEMA P-957, and the weight of 1 ft of each on every square metre or square foot of roof footprint.

SnowDensityWeight of 1 ftRange in the sourceSource
Fresh, dry snow102 kg/m³ (6.4 lb/ft³)6.37 psf (31.1 kg/m²)48–336 kg/m³ (3–21 lb/ft³)EN 1991-1-3 Table E.1; FEMA P-957 §2.2.1
Settled snow (hours or days old)204 kg/m³ (12.7 lb/ft³)12.73 psf (62.2 kg/m²)–EN 1991-1-3 Table E.1
Old snow (weeks old)306 kg/m³ (19.1 lb/ft³)19.10 psf (93.2 kg/m²)255–357 kg/m³ (16–22 lb/ft³)EN 1991-1-3 Table E.1
Wet snow408 kg/m³ (25.5 lb/ft³)25.46 psf (124.3 kg/m²)–EN 1991-1-3 Table E.1
Ice917 kg/m³ (57.2 lb/ft³)57.25 psf (279.5 kg/m²)–FEMA P-957 §2.2.2

FEMA P-957 gives 3 to 21 psf for a foot of fresh snow, from light and dry to wet and heavy: the same depth can weigh seven times as much.

Design snow load by code: one example each

The calculation the tool does, with example inputs rather than a real site. Type the map value for your own address.

  • United States: ASCE 7-16: pg 25 psf, terrain B and sheltered (Ce 1.2), heated (Ct 1), risk category II (Is 1), a 2:12 roof with asphalt shingles: pf = 0.7 × 1.2 × 1 × 1 × 25 = 21.0 psf, Cs = 1, so ps = 21.0 psf (1.01 kN/m²). The minimum for low slopes is 20.0 psf, so 21.0 psf governs.
  • Canada: NBC 2020: Ss 1.1 kPa, Sr 0.1 kPa, Normal importance (Is 1), Cb 0.8, Cw 1, a slippery roof at 16° (Cs = (60 − 16)/45 = 0.978): S = 0.960 kPa (97.94 kg/m²).
  • Europe: EN 1991-1-3 (Eurocode 1): sk 0.85 kN/m², normal topography (Ce 1), Ct 1, 30° (μ1 = 0.8): s = 0.68 kN/m² (69.34 kg/m²). At 45° μ1 falls to 0.4 and s to 0.34 kN/m².
  • Japan: Building Standard Law Enforcement Order, Art. 86: Design snow depth 30 cm at 20 N/m² per cm, 30° (μb = √cos(1.5 × 30°) = 0.841): S = 504.54 N/m² (51.45 kg/m²). A flat roof would carry 600 N/m².

With the other factors at 1.0, a flat roof carries 0.7 × pg under ASCE 7-16, 0.8 × Ss under the NBC (Cb) and 0.8 × sk under Eurocode 1 (μ1). Japan’s Article 86 takes the full design snow depth and reduces only for slope.

How deep can snow get before it reaches a design value?

The depth of each kind of snow that weighs as much as the design value at the top of the column. Your roof’s own value is on its structural drawings.

Snow20 psf (0.96 kN/m²)30 psf (1.44 kN/m²)40 psf (1.92 kN/m²)
Fresh, dry snow37.7 in56.6 in75.4 in
Settled snow (hours or days old)18.9 in28.3 in37.7 in
Old snow (weeks old)12.6 in18.9 in25.1 in
Wet snow9.4 in14.1 in18.9 in
Ice4.2 in6.3 in8.4 in

Where a roof carries more than the average

  • Drifts. Wind piles snow against a higher roof, a parapet, a chimney or rooftop units. Eurocode 1 allows for up to 2.0 × sk beside obstructions (§6.2) and up to 4.0 × sk from wind alone on a lower roof against a taller building (§5.3.6), against 0.8 × sk on an open flat roof.
  • Valleys. Where two slopes meet, snow collects from both sides, and meltwater refreezes in the gutter line.
  • Sliding snow. A steep or metal upper roof can drop its snow onto a porch, canopy or lower roof in one go, with an impact on top of the weight (FEMA P-957 §2.3.1.2).
  • Solar panels. Snow slides off the glass in sheets onto lower roofs and paths, drifts gather between rows and at the lower edge, and the mounting frames stop snow sliding where it otherwise would.
  • Rain on snow. Every millimetre of rain the snow holds adds 1 kg/m², so 25 mm adds about 5 psf. Codes allow for light rain only (FEMA P-957 §2.3.4). Since 15 January 2019, Japan has required a surcharge for rain after snow on light roofs of 15° or less that measure 10 m or more from ridge to eave, outside heavy snow areas.
  • Ice at the eaves. Melting and refreezing build ice dams that stop the snow sliding and load the overhang; a foot of ice weighs about 57 psf.

When to call a structural engineer

FEMA P-957 (§4.2–4.3) lists the warning signs: sagging ceilings or roof members, sprinkler heads dropping below the ceiling, popping, cracking or creaking, bowing truss members, doors or windows that stick, cracked wood members or walls, severe leaks and water pooling on a low-slope roof. If you see any of them, get everyone out of the building and have a structural engineer inspect it.

Removing snow safely

Clear from the ground with a non-metallic roof rake where you can, or hire an insured roofing contractor. Take the drifts first, then work evenly so one side is not left loaded; on a pitched roof go from the ridge towards the eaves. Leave about 5 cm (2 in) of snow to protect the roofing, and keep people away from where snow and icicles fall (FEMA P-957 §5.3).

Sources: CEN, EN 1991-1-3:2003 Eurocode 1, Part 1-3: Snow loads (§5.2 (5.1), Table 5.1, §5.2(8), Table 5.2, §5.3.6, §6.2, Annex E Table E.1); ASCE/SEI, ASCE 7-16 Minimum Design Loads and Associated Criteria for Buildings and Other Structures, Chapter 7 (Eq. 7.3-1, Tables 7.3-1, 7.3-2, 1.5-2, §7.3.4, §7.4, Fig. 7.4-1, §7.10); STRUCTURE magazine, ASCE 7-22 flat roof snow load versus minimum snow load (ASCE 7-22 Eq. 7.3-1, risk-category ground snow loads); ASCE, ASCE Hazard Tool (ground snow load by address); National Research Council Canada, National Building Code of Canada 2020, Division B (Article 4.1.6.2, Table 4.1.6.2.-A, Appendix C Table C-2); e-Gov法令検索, 建築基準法施行令 (第82条, 第86条); 国土交通省, 積雪後の降雨を考慮した積雪荷重の割増し(平成30年国土交通省告示第80号); 長野県, 構造計算における各基準値について(多雪区域の単位荷重); FEMA, Snow Load Safety Guide (FEMA P-957) (§2.2.1, §2.2.2, §2.3, §4.2, §4.3, §5.3). Densities and code factors read on November 17, 2026.

How the load and the code values are worked out

Snow load is depth × density. Eurocode 1 puts settled snow at 2.0 kN/m³, so 30 cm of it weighs 0.60 kN/m² (61 kg/m², 12.5 psf), and on a roof footprint of 80 m² that is 4.89 tonnes. The same depth can weigh far more or less: FEMA gives 3 psf for a foot of light, dry snow and 21 psf for a foot of wet, heavy snow, and a foot of ice weighs about 57 psf. Type the depth and the kind of snow, or weigh a bucket of it, then the roof footprint and pitch. You get the load in kg/m², kN/m² and psf, the total weight on the roof and how it compares with the design snow load from your building plans or from ASCE 7-16, NBC 2020, EN 1991-1-3 or Japan’s Building Standard Law Enforcement Order (Article 86). It is arithmetic, not a structural check, and it cannot tell you that a roof is safe.

How to use this calculator

1

Choose “Snow on my roof now” and metric or imperial units.

2

Type the depth and pick the kind of snow, adding a layer for ice or older snow underneath. Or weigh a bucket of snow, or melt a can-full taken through the full depth.

3

Type the roof size and pitch, and say whether you measured the footprint or along the slope.

4

Type the design snow load from your building’s drawings, or switch to “Design load by code” and send its result to the comparison.

5

Read the load, the total weight and the share of the design value, then print the result or copy the link.

Where people use it

  • •A homeowner after two storms deciding whether the snow on a low-pitched garage roof is worth paying a contractor to clear.
  • •A cabin owner with old snow under fresh snow checking both layers against the design value on the drawings.
  • •A designer turning a ground snow load from the map into a roof value under the code of the country the building is in.

Example: 30 cm of settled snow on a 10 × 8 m roof

30 cm × 203.94 kg/m³ (Eurocode’s 2.0 kN/m³) = 61.18 kg/m², which is 0.60 kN/m² or 12.53 psf. Over a footprint of 80 m² that is 4,895 kg on the roof: 4.89 t or 10,791 lb. At a pitch of 30° the roof surface is 92.38 m², so each square metre of roofing carries 52.99 kg. Against a design value of 1.0 kN/m² the snow is at 60 %. Snow of this density reaches the design value at 50 cm, and the room left equals about 40 cm of fresh snow, 10 cm of wet snow or 41 mm of rain held in the snow.

What this calculator cannot tell you

  • •This is arithmetic, not a structural check. It cannot say a roof is safe: rot, a damaged truss, an undersized beam or a building older than its code can fail below its design value.
  • •Snow is rarely even. Drifts against a higher roof, a parapet or rooftop units and snow in valleys can be several times the average you measured; Eurocode 1 allows up to 2.0 × sk beside obstructions against 0.8 × sk on an open flat roof.
  • •Solar panels shed snow in sheets onto lower roofs and paths, and rows of panels hold drifts between and below them.
  • •Rain on snow adds 1 kg/m² for every millimetre the snow holds. Codes cover light rain only; ASCE 7-16 §7.10 adds 5 psf on some low-slope roofs, and Japan has required a surcharge on large gentle roofs since 2019.
  • •The design value has to be the roof snow load per square metre or foot of footprint, before load factors. A total capacity, a dead load or a factored load cannot be compared with it.
  • •Snow on the ground is not the same depth as on the roof. Measure the roof from a safe place, never by climbing onto it.

Frequently asked questions

How much does snow weigh on a roof?+

It depends on how dense the snow is. Using Eurocode 1’s densities, 10 cm weighs 10.20 kg/m² as fresh snow, 20.39 kg/m² settled, 30.59 kg/m² old and 40.79 kg/m² wet; a foot weighs 6.37, 12.73, 19.10 and 25.46 psf. Ice is 917 kg/m³, so a foot of it weighs 57.25 psf. FEMA gives 3 to 21 psf for a foot of fresh snow, from light and dry to wet and heavy.

How do I calculate the snow load on my roof?+

Multiply the depth by the density of the snow, then by the footprint (plan) area. 30 cm of settled snow at 203.94 kg/m³ is 61.18 kg/m² (0.60 kN/m², 12.53 psf); on a 10 × 8 m footprint that is 4,895 kg. Use the footprint, not the sloped area: loads in every code are per square metre of plan.

How much snow can a roof hold?+

As much as its design snow load allows, which is on the structural drawings or follows from the code for the site. A roof designed for 20 psf (0.96 kN/m²) reaches it under about 38 in (96 cm) of fresh snow, 19 in (48 cm) of settled snow, 9 in (24 cm) of wet snow or 4 in (11 cm) of ice. Drifts can reach it long before the average does.

What is the difference between ground snow load and roof snow load?+

Maps give the load on the ground; codes reduce it for the roof. With the other factors at 1.0, a flat roof carries 0.7 × pg under ASCE 7-16, 0.8 × Ss under the NBC (Cb) and 0.8 × sk under Eurocode 1 (μ1). Japan’s Article 86 takes the full design snow depth and reduces only for slope. Steeper roofs shed snow, so all four reduce the load further with pitch.

Does this use ASCE 7-16 or ASCE 7-22?+

ASCE 7-16, the edition IBC 2018 and IBC 2021 refer to: pf = 0.7·Ce·Ct·Is·pg. ASCE 7-22, referenced by IBC 2024, drops Is from that equation and maps pg separately for each risk category (ASCE Hazard Tool), with a new thermal factor table. If your jurisdiction uses 7-22, do not mix its pg with the 7-16 factors here.

How do I measure snow density with a bucket?+

Push an empty bucket upside down straight into the snow, slide a board under it, turn it over and level the top. Weigh it, subtract the empty bucket and divide by the bucket’s volume: 2.5 kg of snow in a 10 L bucket is 250 kg/m³, and 8 lb in a 5 US gallon bucket is 191.72 kg/m³ (11.97 lb/ft³). After rain, this beats any density table.

When should snow be removed from a roof?+

FEMA P-957 advises removal when the load is close to the roof’s capacity, or somewhat close with more snow forecast. If you see sagging, cracks, creaking or doors that stick, get everyone out and have a structural engineer inspect the building. Clear from the ground with a non-metallic roof rake or hire an insured contractor, take the drifts first and leave about 2 in (5 cm) of snow on the roofing.

How is the snow load calculated in Japan?+

Article 86 of the Building Standard Law Enforcement Order: at least 20 N/m² per cm of snow, or the value of the heavy snow area (Nagano: 30 N/m² per cm or more), times the design snow depth set by the local authority, times μb = √cos(1.5β) for slopes up to 60°. 30 cm gives 600 N/m² on a flat roof and 504.54 N/m² (51.45 kg/m²) at 30°.

Semantic next steps

Continue the calculation

These links move to a different input, formula or project stage rather than a keyword variation of this page.

Free publisher widget

Put this calculator on your website

Give readers the live calculator without rebuilding the math. Copy the responsive embed in one click, or customize width, height, border and corner radius before publishing. The branded MAXScanner attribution stays visible.

Preview

Calculator embed HTML

Paste this code into your page. Focus the code box to select it manually.

Keep the result connected to the real job

MAXScanner keeps the formula and assumptions beside the result so you can verify the number before using it in a drawing, estimate, specification, worksheet or document. Where a supplier, manufacturer, drawing or applicable standard owns a requirement, that source remains authoritative.