The calculation, without hidden assumptions
Check a three-phase supply from three consistent line-to-line RMS readings. MAXScanner shows the average, each deviation, the worst phase pair, percent unbalance and an optional nominal-voltage comparison without confusing NEMA unbalance with voltage regulation or IEC negative-sequence unbalance.
How to use this calculator
Measure Vab, Vbc and Vca at the same location and operating condition using consistent line-to-line RMS readings.
Enter all three measured voltages; optionally enter the system nominal voltage for a separate average-voltage comparison.
Use the maximum-deviation result for NEMA-style motor voltage-unbalance screening.
Investigate uneven single-phase loading, supply issues or high-resistance connections when unbalance is elevated, then re-measure under representative load.
Use the equipment manufacturer or specified power-quality standard when a different unbalance definition or derating curve is required.
Where people use it
- •Screening motor-terminal voltage unbalance during preventive maintenance.
- •Comparing before/after readings when balancing single-phase loads.
- •Finding which line-to-line reading is furthest from the three-reading average.
- •Separating voltage unbalance from simple deviation of average voltage from nominal.
Example: 460 V, 467 V and 450 V
Average = 459 V. Deviations are 1 V, 8 V and 9 V, so maximum deviation = 9 V. NEMA voltage unbalance = 9 ÷ 459 × 100 ≈ 1.961%.
What the result does not assume
- •Use three consistent line-to-line readings for this NEMA maximum-deviation method; do not mix line-to-line and line-to-neutral measurements.
- •This is not the IEC negative-sequence voltage-unbalance-factor calculation. Instruments using symmetrical components can report a different value.
- •The commonly referenced 1% motor threshold is a screening boundary, not permission to infer a specific derating factor. Use the current motor manufacturer/NEMA guidance for derating.
- •A single spot reading may miss load-dependent problems; trend or repeat measurements under representative operating conditions when diagnosis matters.
- •This calculator does not diagnose phase sequence, harmonics, loose connections or insulation condition by itself.
Frequently asked questions
What is the NEMA voltage unbalance formula?+
Calculate the average of the three line-to-line voltages, find the largest absolute deviation from that average, divide it by the average and multiply by 100.
Is voltage unbalance the same as voltage variation from nominal?+
No. Unbalance compares the three phase-to-phase readings with their own average. Nominal deviation compares the average operating voltage with a rated or nominal voltage.
Should I use line-to-line voltages?+
Yes for this calculator. Enter Vab, Vbc and Vca measured consistently at the same location and condition.
Why does a small voltage unbalance matter to motors?+
Three-phase motors can develop current unbalance much larger than the voltage unbalance, increasing losses, heating, vibration and stress.
Is 1% a hard trip setting?+
No. It is a commonly referenced NEMA motor operating threshold. Protection settings and derating must follow the actual motor, relay and applicable standard.
Is the max-min spread divided by average the NEMA formula?+
No. This owner uses maximum single deviation from the average, not the full highest-to-lowest spread.
Semantic next steps
Continue the calculation
These links move to a different input, formula or project stage rather than a keyword variation of this page.
Voltage Drop Calculator — Cable Drop, Max Length, Current & Minimum Area
Calculate voltage drop for copper or aluminum conductors, or reverse-solve maximum cable length, maximum current and minimum mm² area for a chosen drop target across DC, single-phase and balanced three-phase circuits.
Transformer kVA Calculator — Single & Three Phase Load Sizing
Calculate load kVA from voltage and current for single or balanced three-phase systems, then apply an explicit spare-capacity percentage.
Current Unbalance Calculator: 3-Phase Imbalance %
Phase currents of 165.8, 152.7 and 166.6 A average 161.7 A; phase B is 9 A off, so current unbalance is 5.566%. Enter Ia, Ib and Ic to find the worst phase.
Motor Slip Calculator — Synchronous Speed & RPM
Calculate induction-motor synchronous speed, slip RPM, slip percent and rotor electrical frequency from supply frequency, pole count and measured shaft RPM, with optional nameplate comparison.
Ampacity Derating Calculator — Temp & Conductors
Apply ambient-temperature correction and current-carrying-conductor adjustment to an entered starting ampacity, then compare an optional terminal ceiling and load.
Horsepower to Amps Calculator — DC, 1-Phase & 3-Phase
Convert electric horsepower output to estimated input current using voltage, efficiency, phase and power factor, with the input watts and assumptions shown beside the result.
Transformer Efficiency Calculator — Losses & Load
Calculate transformer efficiency at partial load from rated kVA, power factor, core loss and full-load copper loss, with maximum-efficiency loading and 25–100% scenarios.
Power Factor Correction Calculator — Capacitor kVAR & Current Reduction
Calculate capacitor-bank kVAR to raise a lagging load from its measured power factor to a target, with before/after kVAR, kVA and optional line-current comparison.
More in this calculator collection
Browse nearby calculators in the same topic cluster so related pages reinforce each other instead of sitting as isolated URLs.
Free publisher widget
Put this calculator on your website
Give readers the live calculator without rebuilding the math. Copy the responsive embed in one click, or customize width, height, border and corner radius before publishing. The branded MAXScanner attribution stays visible.
Calculator embed HTML
Paste this code into your page. Focus the code box to select it manually.