Voltage Unbalance Calculator — 3-Phase NEMA Method

Calculate three-phase percent voltage unbalance from three line-to-line readings using the NEMA maximum-deviation-from-average method, with phase diagnostics and optional nominal-voltage comparison.

Live calculationWorking shown

Editable live calculator

Change any input — the result updates immediately

No hidden assumptions. Inputs, units and the working stay visible so you can check the calculation.

Calculated result

1.961% voltage unbalance

Average line voltage: 459 V

Maximum deviation: 9 V (Vca)

Highest-to-lowest spread: 17 V

Above the commonly referenced 1% NEMA motor threshold; investigate the supply/load and consult the motor manufacturer for applicable derating guidance.

Average vs entered nominal: -0.22%

Show the working
  1. 1. Average = (460 + 467 + 450) ÷ 3 = 459 V.
  2. 2. Absolute deviations = 1, 8, 9 V; maximum = 9 V.
  3. 3. NEMA percent voltage unbalance = 9 ÷ 459 × 100 = 1.961%.
More actions

Shared links reopen these inputs. Recent and saved calculations stay in this browser unless you clear site data.

The calculation, without hidden assumptions

Check a three-phase supply from three consistent line-to-line RMS readings. MAXScanner shows the average, each deviation, the worst phase pair, percent unbalance and an optional nominal-voltage comparison without confusing NEMA unbalance with voltage regulation or IEC negative-sequence unbalance.

How to use this calculator

1

Measure Vab, Vbc and Vca at the same location and operating condition using consistent line-to-line RMS readings.

2

Enter all three measured voltages; optionally enter the system nominal voltage for a separate average-voltage comparison.

3

Use the maximum-deviation result for NEMA-style motor voltage-unbalance screening.

4

Investigate uneven single-phase loading, supply issues or high-resistance connections when unbalance is elevated, then re-measure under representative load.

5

Use the equipment manufacturer or specified power-quality standard when a different unbalance definition or derating curve is required.

Where people use it

  • •Screening motor-terminal voltage unbalance during preventive maintenance.
  • •Comparing before/after readings when balancing single-phase loads.
  • •Finding which line-to-line reading is furthest from the three-reading average.
  • •Separating voltage unbalance from simple deviation of average voltage from nominal.

Example: 460 V, 467 V and 450 V

Average = 459 V. Deviations are 1 V, 8 V and 9 V, so maximum deviation = 9 V. NEMA voltage unbalance = 9 ÷ 459 × 100 ≈ 1.961%.

What the result does not assume

  • •Use three consistent line-to-line readings for this NEMA maximum-deviation method; do not mix line-to-line and line-to-neutral measurements.
  • •This is not the IEC negative-sequence voltage-unbalance-factor calculation. Instruments using symmetrical components can report a different value.
  • •The commonly referenced 1% motor threshold is a screening boundary, not permission to infer a specific derating factor. Use the current motor manufacturer/NEMA guidance for derating.
  • •A single spot reading may miss load-dependent problems; trend or repeat measurements under representative operating conditions when diagnosis matters.
  • •This calculator does not diagnose phase sequence, harmonics, loose connections or insulation condition by itself.

Frequently asked questions

What is the NEMA voltage unbalance formula?+

Calculate the average of the three line-to-line voltages, find the largest absolute deviation from that average, divide it by the average and multiply by 100.

Is voltage unbalance the same as voltage variation from nominal?+

No. Unbalance compares the three phase-to-phase readings with their own average. Nominal deviation compares the average operating voltage with a rated or nominal voltage.

Should I use line-to-line voltages?+

Yes for this calculator. Enter Vab, Vbc and Vca measured consistently at the same location and condition.

Why does a small voltage unbalance matter to motors?+

Three-phase motors can develop current unbalance much larger than the voltage unbalance, increasing losses, heating, vibration and stress.

Is 1% a hard trip setting?+

No. It is a commonly referenced NEMA motor operating threshold. Protection settings and derating must follow the actual motor, relay and applicable standard.

Is the max-min spread divided by average the NEMA formula?+

No. This owner uses maximum single deviation from the average, not the full highest-to-lowest spread.

Semantic next steps

Continue the calculation

These links move to a different input, formula or project stage rather than a keyword variation of this page.

View the full collection

Voltage Drop Calculator — Forward & Reverse Electrical Solve

Calculate voltage drop and percentage drop, or reverse-solve maximum run, current or conductor area from explicit resistivity and circuit assumptions.

Open

Transformer kVA Calculator — Single & Three Phase Load Sizing

Calculate load kVA from voltage and current for single or balanced three-phase systems, then apply an explicit spare-capacity percentage.

Open

Current Unbalance Calculator — 3-Phase Maximum-Deviation Method

Calculate three-phase current unbalance from Ia, Ib and Ic using maximum deviation from average, with worst-phase diagnostics, spread and an editable review limit.

Open

Motor Slip Calculator — Synchronous Speed, RPM & Rotor Frequency

Calculate induction-motor synchronous speed, slip RPM, slip percent and rotor electrical frequency from supply frequency, pole count and measured shaft RPM, with optional nameplate comparison.

Open

Ampacity Derating Calculator — Temperature & Conductor Adjustment

Apply ambient-temperature correction and current-carrying-conductor adjustment to an entered starting ampacity, then compare an optional terminal ceiling and load.

Open

Ohm's Law Calculator — Volts, Amps, Ohms and Watts

Calculate voltage, current, resistance and power from any two positive electrical values using Ohm's Law and Watt's Law.

Open

Reactance Calculator — Inductive XL, Capacitive XC & LC Resonance

Calculate inductive or capacitive reactance, reverse-solve frequency or component value, or find ideal LC resonant frequency with engineering-unit inputs and visible formulas.

Open

Internal Resistance Calculator — Battery Load Test, Two Points & Voltage Sag

Estimate a source or battery internal resistance from open-circuit and loaded voltage, from two load points, or run the internal-resistance model forward to check sag, loss and efficiency.

Open

More in this calculator collection

Browse nearby calculators in the same topic cluster so related pages reinforce each other instead of sitting as isolated URLs.

Free publisher widget

Put this calculator on your website

Give readers the live calculator without rebuilding the math. Copy the responsive embed in one click, or customize width, height, border and corner radius before publishing. The branded MAXScanner attribution stays visible.

Preview

Calculator embed HTML

Paste this code into your page. Focus the code box to select it manually.

Keep the result connected to the real job

MAXScanner keeps the formula and assumptions beside the result so you can verify the number before using it in a drawing, estimate, specification, worksheet or document. Where a supplier, manufacturer, drawing or applicable standard owns a requirement, that source remains authoritative.