The calculation, without hidden assumptions
Motor efficiency is shaft output power divided by electrical input power. A three-phase motor on 400 V drawing 14.6 A at a power factor of 0.82 takes √3 × 400 × 14.6 × 0.82 = 8.29 kW. If a torque meter reads 49 N·m at 1,460 rpm at the same moment, the shaft delivers 49 × 2π × 1,460 ÷ 60 = 7.49 kW. Efficiency is 7.49 ÷ 8.29 = 90.32%, and the other 0.80 kW turns into heat in the motor. Enter volts, amps and power factor, or a power-analyzer kW reading; then torque and speed, or the shaft kW or hp. The calculator shows every step, converts lb·ft and hp, flags readings that would give more than 100%, and can compare the running cost with a more efficient motor. It does not assign an IE or NEMA Premium class: those come from standard tests at rated conditions, and the table below lists the minimums so you can see where a reading sits.
How to use this calculator
Choose how you know the input: volts, amps and power factor from clamp meters, or the kW a power analyzer shows. For three phase, enter the line-to-line voltage and the average line current.
Choose how you know the output: torque and speed from a torque transducer or dynamometer, or the shaft power in kW or hp. Use the nameplate rating only when the motor really runs at full rated load.
Take every reading at the same steady load. Values from a start-up, a cycling load or different minutes do not describe one operating point.
Read the efficiency with the losses next to it. If the result is above 100%, one of the readings or settings is wrong, usually the phase setting or the power factor.
To weigh a replacement, enter its nameplate efficiency, the running hours per year and your price per kWh. The calculator keeps the shaft output the same and shows the input power, energy and cost difference.
Where people use it
- •Checking a motor on a test bench or dynamometer, where torque, speed and electrical input are measured together.
- •Energy audits: turning measured input power and shaft load into losses and the yearly cost of those losses.
- •Deciding whether to replace an old or rewound motor with an IE3, IE4 or NEMA Premium unit, from the input power the same shaft load would need.
- •Estimating the heat a motor adds to a plant room, from its losses in kW and BTU/h.
Worked example: 7.5 kW, 4-pole motor on 400 V, 50 Hz
Readings at a steady load: 400 V line to line, 14.6 A, true power factor 0.82, 49 N·m on the torque meter and 1,460 rpm. Input power = √3 × 400 × 14.6 × 0.82 ÷ 1000 = 8.294 kW. Angular speed = 2π × 1,460 ÷ 60 = 152.89 rad/s, so shaft output = 49 × 152.89 ÷ 1000 = 7.492 kW (10.05 hp). Efficiency = 7.492 ÷ 8.294 = 90.32%, and losses are 0.803 kW, about 2,739 BTU/h of heat. The EU IE3 minimum for a 4-pole 7.5 kW motor is 90.4%, so this reading sits 0.08 points below it, yet that does not mean the motor fails IE3: clamp meters and torque sensors carry errors of their own, the load is not exactly rated, and EU market checks allow the tested losses (100% − η) to exceed the declared value by up to 15%. Comparing with an IE4 motor at 92.6%: the same 7.492 kW of shaft power would need 8.090 kW, 0.204 kW less. Over 4,000 hours a year that is 816 kWh, about 122.47 at 0.15 per kWh.
| Rated output | IE2, 50 Hz | IE3, 50 Hz | IE4, 50 Hz | US, made June 2016 to May 2027 | US, made from June 2027 |
|---|---|---|---|---|---|
| 0.75 kW (1 hp) | 79.6 | 82.5 | 85.7 | 85.5 | 85.5 |
| 2.2 kW (3 hp) | 84.3 | 86.7 | 89.5 | 89.5 | 89.5 |
| 5.5 kW (7.5 hp) | 87.7 | 89.6 | 91.9 | 91.7 | 91.7 |
| 7.5 kW (10 hp) | 88.7 | 90.4 | 92.6 | 91.7 | 91.7 |
| 11 kW (15 hp) | 89.8 | 91.4 | 93.3 | 92.4 | 92.4 |
| 22 kW (30 hp) | 91.6 | 93.0 | 94.5 | 93.6 | 93.6 |
| 37 kW (50 hp) | 92.7 | 93.9 | 95.2 | 94.5 | 94.5 |
| 55 kW (75 hp) | 93.5 | 94.6 | 95.7 | 95.4 | 95.4 |
| 75 kW (100 hp) | 94.0 | 95.0 | 96.0 | 95.4 | 96.2 |
| 110 kW (150 hp) | 94.5 | 95.4 | 96.3 | 95.8 | 96.2 |
What the result does not assume
- •A measured efficiency does not by itself establish an IEC/NEMA efficiency class, regulatory compliance or nameplate performance. IEC 60034-30-1 assigns IE classes (IE1 to IE5 in the 2025 edition) to motors from 0.12 to 1,000 kW using efficiency determined by the test methods of IEC 60034-2-1 at rated output, rated voltage, rated frequency and 25 °C. A field reading at part load, on a distorted supply or with hand-held instruments answers a different question.
- •The EU rules are in Commission Regulation (EU) 2019/1781: since 1 July 2021 three-phase motors of 0.75 to 1,000 kW with 2, 4, 6 or 8 poles must reach at least IE3, and since 1 July 2023 three-phase motors of 75 to 200 kW with 2, 4 or 6 poles must reach IE4 (brake and explosion-protected motors excepted). The table shows 50 Hz values; 60 Hz IE limits are different numbers.
- •The US limits are in 10 CFR 431.25. Table 5 covers NEMA Design A and B (and IEC Design N) motors of 1 to 500 hp made from 1 June 2016; Table 8 replaces it for motors made from 1 June 2027 and raises several ratings, for example 100 hp 4-pole enclosed from 95.4% to 96.2%. Table 5 follows the full-load levels of NEMA MG 1 Table 12-12, which motor makers sell as NEMA Premium. A kW rating is converted with 1 kW = 1/0.746 hp before the table is read.
- •The three-phase formula assumes a balanced supply. With unbalanced voltages, uneven phase currents or a variable-frequency drive in front of the motor, read the real input kW from a power analyzer and use the kW input option. On a drive output, an ordinary clamp meter does not read the true power factor.
- •Load changes both numbers. The US Department of Energy's guide "Determining Electric Motor Load and Efficiency" notes that motor efficiency usually peaks near 75% of rated load, is almost the same at 50% load as at full load, and drops sharply below 50%; power factor starts to fall at higher loads than efficiency does. The comparison option uses one efficiency for each motor, which is a fair estimate between about 50% and 100% load and an optimistic one below that.
- •Power factor is not efficiency. Power factor tells how much of the current does real work; efficiency tells how much of that real power reaches the shaft. Correcting power factor with capacitors lowers the supply current but leaves the motor's efficiency unchanged.
- •Losses are reported as one figure, input minus output. Splitting them into stator copper, rotor copper, iron, friction and stray-load losses needs the standard test procedure, not one operating point.
Frequently asked questions
How do I calculate the efficiency of an electric motor?+
Divide the mechanical output power at the shaft by the electrical input power and multiply by 100. Both must be real power in the same unit, measured at the same time. For example, 7.492 kW at the shaft from 8.294 kW of input is 90.32% efficiency.
How do I find motor input power from volts, amps and power factor?+
For three phase, multiply √3 by the line-to-line voltage, the line current and the true power factor, then divide by 1000 for kW. The US Department of Energy uses this as Equation 1 in its motor load and efficiency guide: 469.7 V, 37 A and PF 0.763 give 22.97 kW (the guide prints 22.9). For single phase, leave out √3.
How do I calculate shaft output from torque and rpm?+
Multiply torque in N·m by 2π × rpm ÷ 60 to get watts. 49 N·m at 1,460 rpm is 7,492 W, or 7.492 kW. In US units, 29.6 lb·ft at 1,765 rpm is 40.13 N·m and 7.418 kW (9.95 hp); the calculator converts lb·ft for you.
Why does my motor efficiency come out above 100%?+
Because the readings do not belong together. The most common cause is three-phase readings entered as single phase: the 400 V, 14.6 A, 0.82 example without √3 gives 4.789 kW of input and an impossible 156.44%. Other causes are using phase voltage instead of line voltage, power factor left at 1, a torque meter in lb·ft read as N·m, and values taken at different loads.
Can I tell from a measurement whether a motor is IE3 or NEMA Premium?+
No. A class is assigned from standard tests at rated output, voltage and frequency, and the motor's nameplate states it. A field measurement can show that a motor is working well or badly at its present load, but a reading of 90.32% against an IE3 minimum of 90.4% neither proves nor disproves IE3.
How much does a more efficient motor save?+
Keep the shaft output the same and divide it by each efficiency. At 7.492 kW of shaft power, 90.32% needs 8.294 kW and an IE4 motor at 92.6% needs 8.090 kW. The 0.204 kW difference over 4,000 hours a year is 816 kWh. Running hours matter most: a motor that runs 1,000 hours a year saves a quarter of that.
Is power factor the same as efficiency?+
No. Efficiency compares mechanical output with real electrical input. Power factor compares real input with apparent input (volts × amps). The motor in the worked example has a power factor of 0.82 and an efficiency of 90.32% at the same moment, two different numbers that answer different questions.
Semantic next steps
Continue the calculation
These links move to a different input, formula or project stage rather than a keyword variation of this page.
Motor Current Calculator — kW/HP to Full-Load Amps
Estimate single-phase or three-phase AC motor full-load current from shaft power, voltage, power factor and efficiency, with input kW, apparent kVA and adjustable starting-current context.
Motor Torque Calculator — Torque, Power & RPM
Calculate electric motor shaft torque, mechanical power or RPM from any two operating-point values, with N·m, lb·ft, kW and mechanical horsepower results.
Power Factor Calculator — kW, kVA & kVAR
Calculate power factor from real power and apparent power, or derive kVA and reactive power from kW and a known power factor.
Three-Phase Power Calculator — kW, kVA, kVAR & Power Factor
Calculate balanced three-phase apparent, real and reactive power from line-to-line voltage, current and power factor, with phase angle shown for the simplified power triangle.
Power Unit Converter — W, kW, MW, HP, PS, BTU/h & Refrigeration Tons
Convert power between W, mW, kW, MW, GW, mechanical hp, metric PS, BTU/h, kcal/h, refrigeration tons and ft·lbf/s, with all equivalents and explicit power-vs-energy guidance.
Motor Slip Calculator — Synchronous Speed & RPM
Calculate induction-motor synchronous speed, slip RPM, slip percent and rotor electrical frequency from supply frequency, pole count and measured shaft RPM, with optional nameplate comparison.
Horsepower to Amps Calculator — DC, 1-Phase & 3-Phase
Convert electric horsepower output to estimated input current using voltage, efficiency, phase and power factor, with the input watts and assumptions shown beside the result.
Ohm's Law Calculator — Volts, Amps, Ohms & Watts
Calculate voltage, current, resistance and power from any two positive electrical values using Ohm's Law and Watt's Law.
Torque conversions
Horsepower and kilowatts
More in this calculator collection
Browse nearby calculators in the same topic cluster so related pages reinforce each other instead of sitting as isolated URLs.
Free publisher widget
Put this calculator on your website
Give readers the live calculator without rebuilding the math. Copy the responsive embed in one click, or customize width, height, border and corner radius before publishing. The branded MAXScanner attribution stays visible.
Calculator embed HTML
Paste this code into your page. Focus the code box to select it manually.
Keep the result connected to the real job
MAXScanner keeps the formula and assumptions beside the result so you can verify the number before using it in a drawing, estimate, specification, worksheet or document. Where a supplier, manufacturer, drawing or applicable standard owns a requirement, that source remains authoritative.